All Seasons Hire Hot Block 25 Operating Instructions Download Page 2

General Safety 

The units are designed for "indoor" use only. 
 
The units should be mounted on the floor. if this is impossible 

ensure that they are provided with a very stable platform. 
 
Do not position on surface water or where airborne water 
(liquid) is present. 

 
Position the unit to allow clear air input and exit from the unit.  
A minimum distance of 2 meters should be allowed between 

the outlet nozzle of the heater and any obstruction. 
 
Do not use the units when surrounded by combustible 
materials. 

 
Maximum surrounding air temperature 40°C 
 

 
 
 

Electrical Safety 

The units must be installed in compliance with the appropriate 
requirements of the I.E.E. Regulations, 15th Edition. 
 

The units must only operate in conjunction with a permanent 
earth connection. 
 

The electrical supply should be appropriately protected by fuse 
or circuit breaker as follows:- 

Hot Block 25 

240 Volt 

 

13 -16 Amps maximum 

Hot Block 25 

110 Volt 

 

32 Amps maximum 

Hot Block 65 

415 Volt 

 

20 Amps/phase maximum 

Hot Block 95 

415 Volt 

 

32 Amps/phase maximum 

 
For use on construction sites refer to CP1017 - Electrical 
Distribution on Building Sites. 

 

Trouble Shooting 

 
ALWAYS ISOLATE UNIT FROM ELECTRICITY SUPPLY BEFORE MAINTENANCE 

 
 
 

Fault 

 

Likely Problem 

Remedial Action 

No fan 

 

No electricity supply 

Check fuses/breakers. 

 

 

 

 

 

 

Check supply cable. 

 

 

 

 

 

 

*Meter heater terminal block 

 

 

 

 

 

 

for correct supply voltage. 

 

 

 

 

 

 

Meter selector switch for 

 

 

 

 

 

 

continuity. 

 

 

 

 

 

 

Check security of terminals and 

 

 

 

 

 

 

cables. 

 

 

 

 

 

 

Check fan blade is secure on 

 

 

 

 

 

 

motor shaft. 

 

 

 

 

 

 

Exchange motor. 

No heat 

 

Lack of air 

 

*Meter correct voltage at unit. 

 

 

 

 

 

 

Ensure clear access for air 

 

 

 

 

 

 

through unit. 

 

 

 

 

 

 

Check fan as above. 

 

 

 

 

 

 

Check that heat returns after 

 

 

 

 

 

 

cool down period. 

 

 

 

 

 

 

If unit continues to cycle, 

 

 

 

 

 

 

identify faulty overheat  

 

 

 

 

 

 

protector and exchange. 

 

 

 

 

 

 

Check for continuity through 

 

 

 

 

 

 

each heating element and 

 

 

 

 

 

 

exchange as appropriate. 

 
 

*NOTE: A valid check of the correct voltage at the unit can only be carried 
out when the unit is operating under full load. This requires the unit to be 
run with covers removed. Any fault finding work should be carried out by a 

qualified electrical engineer and the unit run with covers off for the 
minimum period possible. During maintenance always check that all 

components are securely mounted and that all electric terminals are tight. 

 
 

 
 
 

 

Reviews: