2
4.
Stove installation
During stove installation you should follow valid regulations regarding the construction and firefighting requirements. The
placement site should be horizontal and with sufficient bearing capacity, otherwise the appropriate measures must be applied for
equal load distribution. In case of flammable floor (wood, plastics, textile...) it is necessary to put steel-sheet, copper or other
inflammable material on the floor beneath the stove. Such base must cover the stove profile for at least 30 cm, and on the operation
side it should be greater in length by 50 cm.
Fig.5
There should be enough space between the stove and flammable objects (with wooden sheeting, furniture, curtains etc.). The
distance between the wooden parts of furniture or plastics and other flammable objects to be protected must be at least 50 cm to
the sides and 50 cm on the back (Figure 5). There should be a distance of 90 cm at least between flammable objects from the stove
filling opening.
Installation of objects above the stove is forbidden if the cast panel is used.
During the installation of used air drain pipe it is necessary to secure the distance of at least 50 cm away from flammable
materials.
Before the stove is connected to the chimney it is mandatory to consult the local competent chimney sweeping organization.
The flue-stove connection is done through the connecting elements according to SRPS.M.R4.031 (DIN 1298 or DIN EN 1856-2).
Make sure that the chimney fittings do not protrude from the cross-section into the waste gas drain pipe, as well as that they have
proper sealing function.
To achieve the best stove operation, the installation should be performed properly and perfect chimney should be provided. In
any case it is necessary to inspect the existing flue pressure before the commissioning through the placement of lighted candle
beneath the flue inlet. Chimney draught is considered sufficient if the flame bends towards the flue inlet. Slight flame bending
indicates insufficient draught. The area where the appliance is installed should have satisfactory fresh air supply (Figure 6).
If two fireboxes are installed on a single chimney within a single floor (multiple engagement), the distance between the
connections must not be less than 50 cm.
Fig.6