3.3 Electrical installation, Digital-IO 24V
1
a) Remove the top cover by turning it
counter clockwise and then lifting it
upwards.
b) Connect the cable to the ThinkTop, and
then connect the wires to the terminals
according to the wiring diagram.
c) Tighten the cable gland using a 19 mm
wrench (3 Nm).
Or tighten the M12 connector using a 14
mm wrench (0.6...1.5 Nm).
d) Put the top cover back in place.
e) Turn on the power supply.
If installed correctly, the light guide flashes
green.
2066-0048
e
a
d
c
b
Wiring diagrams
Terminals V50 Digital-IO 24V
1
Power supply
24V
(brown)
2
Power supply
GND
(blue)
3
out (PLC in)
Status OK
(white)
4
out
Valve de-energised (DE-EN)
(black)
5
out
Main valve energised (EN)
(grey)
6
in
Solenoid valve 1 for main valve (SV1)
(pink)