![Alfa Laval ThinkTop V50 Instruction Manual Download Page 10](http://html.mh-extra.com/html/alfa-laval/thinktop-v50/thinktop-v50_instruction-manual_2895002010.webp)
3.1 Mechanical installation
Mechanical installation is a two-step process, where you mount the sensor target to the actuator stem
and the ThinkTop to the actuator top.
1
Fit the yellow sensor target to the actuator
stem.
Tighten the sensor target by hand or by using
a 2.5 mm hex key (1...2 Nm)
2066-0038
2
Mount the ThinkTop centred and flat against
the actuator top.
Hold the ThinkTop flat and steady against the
actuator top.
Use a 2.5 mm hex key to lightly tighten one of
the two set screws.
Tighten the second set screw (1...1.5 Nm).
Tighten the first set screw (1...1.5 Nm).
2066-0040
NOTE
While you can perform the mechanical installation of a seat lift sensor at this time, the
electrical installation must be completed before you can test the seat lift sensor. For
information on how to install and test the seat lift sensor, see Install the seat lift sensor
on page 16.