6 Setup diagram
Enter Setup
Step 1 –
B
5s
Save and Exit
D
NextC
5s
Exit no change accepted
step E
F
A
Step 2 – Setup valve type
B
Default
SRC/ARC
LKB
Unique Mixproof
SMP-SC
Unique 7000
+/- 5mm
Series 700
(LKLA-T)
SMP-SC
SMP-BC
Unique Mixproof PMO/Curd
D
(O
Only used
SRC-PV
SMP-TO
Unique Mixproof CP3/LP
NextC
when self
AMP
SMP-BCA
Unique Mixproof HT/VT
step E
adjustment
SBV
Unique Mixproof 3A
F
feature is
Unique SSV
A
required)
SRC/ARC
Next
Series 700
step
S
Step 3 – Set closed position
B
Default
Position stored
D
NextC
step E
F
Activate the valve to the closed position
(De-energized)
auto
A
S
Step 4 – Set open position
B
Default
Position stored
Next D
step C
E
auto
F
Activate the valve to the open position
(Energized)
S
Step 5 – Set upper seat lift
B
Default
Position stored
Next D
step C
E
F
Activate the valve to upper seat lift. When
using an external sensor the sensor must
be active when ””II” is pushed
auto
A
S
Step 6 – Set lower seat lift
B
Default
Position stored
D
NextC
step E
F
Activate the valve to lower seat lift. When
using an external sensor the sensor must
be active when ””II” is pushed
auto
A
S
Step 7 – Set self adjust (Recommended: Disabled)
B
Default
Associated
Associated
Associated
Disabled
with
with
with
Next D
closed/
closed
open
step C
open
position
position
E
position
F
A
Next
step
S
Step 8 – Setup maintenance
B
Default
90 days
180 days
270 days
360 days
+90 days
Disabled
(Up to
Next D
max.
step C
18 years)
E
F
A
Next
step
23