7
2
-
1 Performances
ATLX Model
The
ATLX
heaters are equipped with an axial fan for a
direct blowing into the room.
It is designed to be installed outside or inside a room to
heat.
It is equipped in series with 2
-
stages solenoid gas valve
to meet as much as possible the heating needs.
2
-
2 Dimensions
Types
ATLX55
ATLX85
A (mm)
740
1120
B (mm)
1130
1130
C (mm)
1110
1110
D (mm)
462
462
E (mm)
145
145
Fumes (mm)
Ø 80
Ø 80
Gas (mm)
3/4’’
M
3/4’’
M
TYPES
ATLX55
ATLX85
Gas Input
kW
51,7
84,7
Nominal Output (Prated,h)
kW
48,1
78,5
Efficiency at Nominal heat output (ƞnom)
%
92,9
92,7
Minimal power (Pmin)
kW
33,9
55,0
Efficiency at minimal power (ƞpl)
%
94
93,8
Fan
Ø [mm]
1x Ø450
2x Ø450
Speed rotation
RPM
1350
1350
Air flow at 15 °C
m3/h
4 800
9 000
Gas flow at 15°C
-
Natural G20
-
Groningen G25
-
Propane G31
20 mbar
25 mbar
37 mbar
5.3 m3/h
5.9 m3/h
3.9 kg/h
8.5 m3/h
9.5 m3/h
6.3 kg/h
Smoke exhaust diameter
Ø [mm]
80
80
Supply voltage
Monophasée 230 Volts / 50 Hz
-
IP54
Electrical power
W
670
990
Electrical current
A
3
4,5
Electrical Consumption (Blowing fan excluded)
At Nominal heat output (elmax)
kW
0,14
0,14
At Minimal power (elmin)
kW
0,1
0,1
Emissions of nitrogen oxides (Nox)
mg/kWh
< 99
< 99
Seasonal energy efficiency for space heating (ƞs,h)
%
74,79
75,46
Operating temperature
°C
0/+40°C
Weight
kg
200
280