The junction box is used to connect the damper's servomotor cable to the "RG" connecting cable. When there are two dampers (air inlet and outlet), 
the two servomotor cables are connected in parallel. Wire the equipment (see diagram below) according to the configuration - one or two dampers.

1 fresh air or discharged 

air damper only

Black strand

Red strand

Three-way connector

Three-way connector

Junction box

Towards terminal block

Towards damper

Two fresh air or discharged 

air dampers in parallel

Black strand

Red strand

Three-way connector

Three-way connector

Junction box

Towards terminal block

Towards damper

Damper servomotor cable

RG cable

Damper servomotor cable

Damper servomotor cable

RG cable

Once this wiring has been completed, shut-off damper side, wire the equipment electronic board side.
To ensure that the junction box is leaktight, thread the "RG" cable through one of the right-hand cable glands PG9, located under the junction box. 
Connect the two "red and black" strands in the "RG" cable to the two terminals of connector "1". See diagram below:

Caution:

 the strand 

 must be connected to the +24V and the strand 

 to the earth.

Pas de neutre 

sur la VEX410

Pas de neutre 

sur la VEX410

No neutral on VEX410

No neutral on VEX410

 

See Section 3.2.3 for shut-off damper dimensions.

Summary of Contents for VEX400

Page 1: ...www aldes com VEX400 Installation and maintenance manual EN...

Page 2: ...s 9 2 7 3 Installation of air inlet outlet damper 9 2 7 4 Connection of standard flexible sleeves 11 2 7 5 Connection of the CO2 sensor 11 2 7 6 Internal water coil option 12 2 7 7 Constant pressure o...

Page 3: ...ONS 19 3 1 Unit dimensions 19 3 2 Outside accessory dimensions 19 3 2 1 Roof cowl 19 3 2 2 Rain hoods 20 3 2 3 Shut off dampers 20 3 2 4 Adapter drawings 20 3 2 5 Flexible sleeve drawings 21 4 CONTROL...

Page 4: ...2 9 4 of the installation manual The product s power supplies must be switched off before any maintenance or cleaning operation Make sure that the unit cannot start running accidentally If one of the...

Page 5: ...30 screws M6 The unit s rating plate is duplicated One plate is located on the back of the quick access hatch and another on the side panel The unit is packed in plastic film protected with cardboard...

Page 6: ...probes transparent tubes and pressure taps are pre connected on stand by in the side rail air supply side All the notices for the use of the unit are behind the new air filter access door An SD board...

Page 7: ...installation and Section 3 for the dimensions 2 5 Airflow direction There is a right hand and a left hand version 2 5 1 Right hand version Fresh air Discharge Extraction Air supply Fresh airflow towar...

Page 8: ...onents to guarantee a uniform temperature in the section Drill a hole between 21 mm and 30 mm in the duct so that the probe and gland can be threaded through Apply a bead of mastic to the metal plate...

Page 9: ...rged air towards fresh air plan for at least 4 mm between the air inlet and outlet see DTU 68 3 part 1 1 4 for residential buildings For service buildings the RSDT makes it mandatory for the extract a...

Page 10: ...r Three way connector Junction box Towards terminal block Towards damper Damper servomotor cable RG cable Damper servomotor cable Damper servomotor cable RG cable Once this wiring has been completed s...

Page 11: ...s one female outlet and a module OJ Air LON The assembly is pre wired and factory fitted at the connection terminal block Connect the cable RJ12 labelled R11 on stand by in the side rail to one of the...

Page 12: ...on outside equipment or equipment located in a moist environment must be watertight It is recommended to protect the connections between the servomotor cable and the Water Bat cable by at least class...

Page 13: ...tubes are equipped with pressure taps and identified by a pression insufflation supply pressure label to measure the air supply pressure and pression extraction extract pressure to measure the extract...

Page 14: ...with diaphragm Condensate evacuation direction nit Watch out for the risk of frost in winter plan to insulate the water trap and the evacuation manifold if they are in an unheated atmosphere 2 8 2 Co...

Page 15: ...forget to connect the earth 2 9 1 Control Power principle Every unit has an electrical connection box on the front panel This box gives access to the electrical power and control components disconnect...

Page 16: ...power cable conductors that are rigid or fitted with end pieces are screwed in the fixed body of each switch 2 9 3 General power connection single phase of the unit Thread the power cable through the...

Page 17: ...lable timer or a clogging indicator sold as an option filter fouling 2 10 1 Filter replacement following timer This timer according to the factory setting will trigger after three months the user can...

Page 18: ...lacement following timer The remote control is fitted with a display a confirm button two navigation buttons or and eight indication LED Please refer to the configuration guide to configure the machin...

Page 19: ...fixing F x G mm Weight kg VEX410 1505 578 628 904 440 x 240 160 VEX420 1822 578 628 1157 440 x 340 205 VEX430 1825 910 954 1157 740 x 340 291 VEX440 2166 910 954 1468 640 x 440 366 3 2 Outside accesso...

Page 20: ...25 3 2 3 Shut off dampers F 85 130 4 x 1 0 D B C A E A mm B mm C mm D mm E mm F mm VEX 410 270 470 240 440 210 410 VEX 420 370 470 340 440 310 410 VEX 430 370 770 340 740 310 710 VEX 440 470 670 440 6...

Page 21: ...21 3 2 5 Flexible sleeve drawings D B C A E A mm B mm C mm D mm E mm VEX 410 270 470 240 440 250 VEX 420 370 470 340 440 315 VEX 430 370 770 340 740 355 VEX 440 470 670 440 640 500...

Page 22: ...4 of the connection diagram above and configuration guide CO2 probe control of the fan speed according to the CO2 concentration level in the room to be treated see terminal block 4 of the connection d...

Page 23: ...23 NOTES...

Page 24: ...www aldes com 11072615 A 12 2019 RCS 956 506 828 Imprim en France Printed in France...

Reviews: