2.9.3 Unit General power supply
We recommend a 20A circuit breaker with a sensitivity differential of 300mA and a 1.5mm2 section cable for the general power supply.
Caution:
three-phase power supply from the VEX560 (4500 XH) unit.
Unit power supply
Models
Power supply
Frequency
Max. power
consumption (W)
Type of terminal
VEX520
1 ~ T
50Hz
1000
Snap-lock
connector terminal
- cable section
0.14 to 4 mm ² -
rigid conductor or
crimped contacts
recommended
VEX525
1 ~ T
50Hz
1000
VEX530
1 ~ T
50Hz
1000
VEX540
1 ~ T
50Hz
1420
VEX550
1 ~ T
50Hz
2720
VEX560
3 ~ N +T
50Hz
4420
VEX570
3 ~ N +T
50Hz
5020
VEX580
3 ~ N +T
50Hz
7220
Connection
power supply terminals
VEX520 - 525 - 530
VEX540 - 550
unit single phase 230V+T:
- 2 Motorised-Fans
extraction/blowing
- PLC
3(
/
1
$1
$/
$7
$1
$/
$7
Power supply terminal connection
VEX560 - 570 - 580
unit three phase power supply
3 x 400V +N +T :
- 2 Motorised-Fans
extraction/blowing
- PLC
3(
/
/
1
/
$1
$/
$/
$1
$7
$/ $/
$/ $7
$/