EC3-33x Coldroom Controller with EX5

User Manual

EC3-33x

A.6.5.063E - Rev 4

4

Emerson Electric GmbH & Co  -  ALCO CONTROLS  -  Heerstr. 111  -  D-71332 Waiblingen  -  Germany - Tel.: ..49 (0) 7151 509 0 - Fax: 49 (0) 7151 509 200

Remarks

 

/1  Value to be shown on display

0 = Thermostat control temperature, Alignment factor /C will
only work with this temperature display
1 = Air in temperature
2 = Air out temperature
3 = Alarm temperature
4 = Defrost termination temperature
5 = Coil in temperature
6 = Coil out temperature
7 = Superheat
8 = Valve opening
9 = Defrost status
10 = not used
11 = not used

 

/2 No alarms

0 = alarms will be shown on display
1 = alarms will not be shown on display

 

/5 Temperature unit for display

0 = °C
1 = °F

 

/6 Display with decimal point

0 = yes, in the range from –19.9 to 19.9
1 = no

 

/7 Display during defrost

0 = “df”
1 = “df” + defrost termination temperature
2 = “df” + control temperature

 

r0 Door contact function

Contact closed or nviDoor = ST_ON
Value = C  Alarm + Timer + Action

Cooling   0 = cooling
                1 = no cooling

Alarm     0 = temperature alarm on, door alarm
              2 = temperature alarm off, door alarm off

Timer     0 = Timer not started
              4 = Timer started

Action when timer expired
              0 = temperature alarm on, door alarm
              8 = temperature alarm on, door alarm,
                    cooling restart if “Cooling = 1”

 

r4 Thermostat mode

0 = off, no thermostat function, continues cooling

       

air in and air out sensor monitoring off, no temp. alarms

       

generated

1 = cooling, deadband control
      cut in   = set-point + difference
      cut out = set-point
2 = cooling, modulating thermostat
      cut in   = set-point
      cut out = set-point – difference /2
3 = heating, deadband control
      cut in   = set-point – difference
      cut out = set-point
4 = on, external control by nviValve
       air in and air out sensor monitoring off, temp. alarms

       

will be generated

 

A0 Mean factor alarm temperature

 

r8  Mean factor day operation

 

r9  Mean factor night operation

Temperature calculation by the following formula

(

)

(

)

100

/

*

MeanFactor

Air

Air

Air

e

Temperatur

out

in

in

=

Mean factor = 0    , Temperature = Air in
Mean factor = 100, Temperature = Air out

 

d0 Defrost mode

0 = natural defrost, defrost heater not activated
      pulsed defrost not possible, synchronization by bindings
1 = forced defrost, defrost heater activated, pulsed
      defrost possible, synchronization by bindings
2 = forced defrost, defrost heater activated, pulsed
      defrost possible, synchronization by nviStartUp

 

d1 Termination by temperature / time

0 = termination by temperature, termination by time
      will generate an alarm
1 = termination by time, termination by temperature
      will generate an alarm
2 = first, what ever comes first time or temperature,
      no alarm
3 = last, by time and temperature, no alarm

 

d2 Defrost termination sensor

0 = defrost termination sensor
1 = air out sensor

 

d3 Pulsed defrost

0 = off, no pulsed defrost, heaters switched off at
      defrost termination temperature dt or max. time
      dP whatever is selected
1 = on, pulsed defrost, dd and dH in use, heaters are
      switched off at dH and switched on again at
      dH – dd

 

d6 Pump down delay

The compressor will run during pump down delay while
the valve is closed

 

d8 Injection delay

The valve is open during injection delay while the
compressor is not running

 

d9 Demand defrost mode

0 = demand defrost off
1 = on
2 = on + defrost if no demand defrost within dI

 

F1 Start up sequence after defrost

0 = on
1 = delayed by time Fd, error on temperature
2 = by temperature Ft, error on time
3 = first, whatever comes first time or temperature,
      no alarm
4= last, time and temperature must come, no alarm

 

F2 Fan status during no cooling

0 = on
1 = off
2 = delayed by F4

Summary of Contents for EC3-33x

Page 1: ...EC3 33x User Manual Rev 4 14 01 2003...

Page 2: ...ill return to the by 1 selected data NEURON ID SERVICE BUTTON Display Press the button for app 1 second to send the Neuron ID An LED in the left upper corner will indicate the transmission of the Neur...

Page 3: ...1 flag 1 d3 Pulsed defrost 0 1 flag 0 d4 Defrost at power up 0 1 flag 0 d5 Delay for power up defrost 0 180 min 0 d6 Pump down delay 0 180 sec 0 d7 Drain delay 0 180 min 2 d8 Injection delay 0 180 se...

Page 4: ...in and air out sensor monitoring off temp alarms will be generated A0 Mean factor alarm temperature r8 Mean factor day operation r9 Mean factor night operation Temperature calculation by the followin...

Page 5: ...eaning 0 off 1 on u0 Refrigerant 0 R22 1 R134a 2 R507 3 R404A 4 R407C u1 Correction Glide positive Values Pressure drop negative Values u2 MOP Control 0 off 1 on u4 Control Mode 0 off 1 fixed superhea...

Page 6: ...n failure by time or temperature Ft Fan start up failure by time or temperature Ab external battery alarm external battery indicates an alarm MESSAGES No data The display will show an at node start up...

Page 7: ...ressor failure Door contact Switch 1 Switch 2 oil in oil out Air in temp Air out temp Defrost termination temp Temp 6 Switch 24V AC DC or 230V AC Sensor NTC 10K at 25 C Pressure Sensor PT3 07 4 20 mA...

Page 8: ...BL BK WH Battery Fail 24V AC Fan DI 1 8 24V AC DC or 230V AC DI 9 12 24V AC DC only DO 250V max 8A 2A Comp Heater Alarm Relay Door Comp safety Di3 Di4 Do1 1 C 2 Do2 1 C 2 Do3 1 C 2 Do4 1 C 2 LON A B...

Page 9: ...sensors is between 9 and 3 o clock as shown on the picture The air sensors must be mounted on spacers in the middle of the air duct so that the air flow around The recommended positions in detail 1 S1...

Page 10: ...nding on cable type Transfer rate 39 kbits s FTT10 Structure free topology Termination RC Network Medium Twisted pair 2 wires Connection 11 12 Data 13 free Nodes Segment 64 Units Cable length max 2700...

Page 11: ...0 7151 509 0 Fax 49 0 7151 509 200 NODE OBJECTS The EC3 33x coldroom controller has 11 LonMark Objects EC3 33x Node Object Compressor Object 20004 Display Object 20006 Analog Sensor Object 20008 Evapo...

Page 12: ...all objects in the node to normal operation RQ_DISABLED This requested object is disabled output network variable of the object will not longer be updated The object will not reacted on input network...

Page 13: ...ostat object SNVT_temp_p nvoAlarmAirTemp O Alarm temperature used by thermostat object SNVT_temp_p nvoAirOutTemp O Air out sensor temperature SNVT_temp_p nvoAirInTemp O Air in sensor temperature SNVT_...

Page 14: ...on unsigned short MeanNight 0 100 50 y y y 5 17 rd Difference day operation unsigned short DiffDay K 0 1 20 2 0 1 y y y Diff between cut in cut out 18 St Setpoint day operation signed long SpDay C r1...

Page 15: ...oDefrTemp O Currently used defrost termination temperature SNVT_lev_disc nvoHeater O Status of the defrost heater SNVT_lev_disc nviStartUp I Input to terminate a synchronized defrost ST_ON will start...

Page 16: ...14 dI Def r ost t i m ei nt er val unsi gnedshor t I nt er val Ti m e h 0 192 8 y y y Ti m e i nt er v al bet ween t w odef r ost cycl es 15 dU St ar t up del ay unsi gnedshor t St ar t UpDl y m i n...

Page 17: ...l control 8 1 Termination error Configuration Parameters Fan UNVT_FAN Code Description Variable type Name Unit Min Max Default Res IR Kb Lon 0 F1 Fan startup sequence after defrost unsigned short Star...

Page 18: ...ct SNVT_lev_disc nviCompSafety Failure input for compressor safety ST_ON compressor off and locked UNVT_COMP nciCompCnfg C Configuration parameters of the fan object The network variable nvoCompStatus...

Page 19: ...pad unsigned short IrKb 0 3 3 y y y 1 1 H3 IR access code unsigned short IRCode 0 199 0 y y y 2 H5 Password unsigned short PassWord 0 199 12 y y y 3 1 Value to be shown unsigned short Data 0 11 0 y y...

Page 20: ...ircuit E2 6 Air out sensor open E3 7 Air out sensor short circuit E3 8 Defrost termination sensor open E4 9 Defrost termination sensor short circuit E4 10 Temperature 6 sensor open E5 11 Temperature 6...

Page 21: ...perheat object SNVT_temp_p nvoEvapOutTemp O Currently used coil out temperature of the superheat object SNVT_switch nviForcedValve I Manual control of the valve output SNVT_temp_p nvoSuperheatRef O Cu...

Page 22: ...n n y 5 9 uu Start up opening unsigned short Opening 50 100 100 y y y 10 ut Valve type unsigned short ValveType 0 3 0 y y y 7 11 Data source unsigned short Sensor 0 31 0 n n y 6 Total 13 bytes 1 0 R2...

Page 23: ...trols the relays and the TRIAC If the object is disabled the object will not react on any network variable update and the digital outputs will stay unchanged Network Variables Variable Type Name Type...

Reviews: