Passive glass break detector 

Instruction manual 

GD 335

DESCRIPTION 

GD 335 is a passive glass break detector glued on the glass 
surface. The detector is designed in the form of two-ter-
minal component. It has to be connected to Control and 
Indication  Equipment  (CIE)  or  another  specialized  inter-
face unit like IU 300, in alarm loop configured as EOL/NO 
(End-Of-Line – Normally Open). 

EOL resistor has to be placed at the end of the alarm loop 
providing  continuous  analogue  communication  with  CIE 
drawing fixed value of current. 

The detector has high resistance in normal state and does 
not draw any current from EOL loop. It has a latching cir-
cuit lowering rapidly its internal resistance during alarm. 
Increase of current consumption from EOL loop is signal-
ling intrusion to CIE. 

It is specifically designed for surveillance of: 

 

shop-windows 

 

glass sliding doors  

 

single-glazed windows  

 

other vulnerable glass surfaces in public offices and 
private homes. 

GD 335 complies with: 

 

EN 50131-2-7-2:2012, security grade 2 

 

EN 50130-5:2011, environmental class IIIA 

FEATURES 

 

Detects glass break of float glass  

 

Large coverage area 

 

Very resistant to disturbances on the glass 

 

No sensitivity adjustment  

 

Ideal for 24-hour loop perimeter protection 

 

Leads are polarity independent 

 

Low current consumption 

 

Completely sealed plastic casing 

OPERATING PRINCIPLE 

GD  335  is  equipped  with  a  piezoelectric  sensor  that  de-
tects  mechanical  waves  propagating  in  the  glass  pane. 
During  glass  breakage,  a  very  short  vibration  pulse  with 
high amplitude and very high frequency contents is gen-
erated and propagates with high speed in the glass. This 
pulse  triggers  the  detector,  changing  its  voltage/current 
characteristics. 

 

Detector has high resistance in normal state and 
practically does not draw current from EOL loop 

 

Detector draws maximum of 7.5 mA in alarm state 
from EOL loop signalling intrusion to CIE 

WIRING 

#  Signal 

Wire colour code  

Function 

Description 

1  a1 

White 

Terminal a: (-) or (+) 

Terminal a (a1, a2 - shorted) 

2  a2 

White 

Terminal a: (-) or (+) 

3  b1 

White 

Terminal b: (+) or (-) 

Terminal b (b1, b2 - shorted) 

4  b2 

White 

Terminal b: (+) or (-) 

Wire identification hints: 

 

Shorted wires are marked with an additional small label  

 

Shorted lines  be also easily identified with the help of ohm-meter, as both pairs consist of 2 wires shorted inside 
detector 

CIRCUIT DIAGRAM 

 

GD 335

a2

b2

a1

b1