background image

IV.

Mechanical Drawing

All dimensions are in centimeters

39.1

2.95

0

25.2

4.60

0

34.4

11.0

4.92 TYP

38.1

30.6

7.62

KEY LOCK

28.0

0

5.38

0

0

0

0

0

V.

Power Limited Wiring Requirements

VI.

Troubleshooting Guide

Fault Output

v

Form "C" Relay Contacts rated 1 Amp @
24VDC.

v

Relay Contacts labeled in the non-operational
(fault) condition.

v

Fail-safe; active until an actual fault condition.

Visual Indicators

1. AC Presence   LED1:    Green LED
2. System OK      LED3:    Green LED
3. LED2 (Red LED) serves no user function.

Fault Conditions
Green LED extinguishes on:
     Low AC / No AC / Blown AC Fuse
     Low Battery / Output
     Blown Battery Fuse

VII

Troubleshooting Chart

Rewire battery set.

Incorrect battery
hook-up.

Remove primary power and batteries, then
replace fuse. CAUTION.

Blown battery fuse.

4) No battery back-up

Verify switch settings in Section III.

Incorrect switch
setting.

Measure xfmr secondary voltage. If not within
proper range, replace transformer.

Incorrect or defective
xfmr.

Rewire battery set.

Incorrect battery
hook-up.

Remove system load and batteries; check
system output voltage. If OK recheck system
requirements, and/or measure output current
draw with an ammeter.

The system load is
greater than the
supply capability.

Check battery condition and replace if needed.

Defective battery.

3) Incorrect output voltage

Check xfmr secondary voltage at PC board
"Low Voltage AC Connection". If voltage is not
present, replace xfmr.

Loss of transformer
(xfmr) power.

Remove primary power and batteries, then
replace fuse. CAUTION.

Blown AC fuse.

Check AC primary supply.

Loss of AC power.

2) Green "AC" LED is not
illuminated.

See Symptom 4.

Blown battery fuse.

See Symptom 3.

Low battery.

"Fault" Relay Contacts transfer.

See Symptom 2.

Low AC / No AC /
Blown AC fuse.

1) Green "System OK" LED
extinguishes. 

Correction Procedure

Possible Cause

Symptoms

            Power Supply/Battery Chargers

                      Installation Instructions

AlarmSaf

 

w

 

65A Industrial Way 

w

 Wilmington, MA 01887-3499 

w

 (978) 658-6717 

w

 FAX: (978) 658-8638  Web Site:  www.alarmsaf.com

52-008B
032497

AC FUSE  (AGC-10)

BATT FUSE  (AGC-10)

Power-limited and nonpower-limited circuit wiring must remain separated by at least 1cm within the cabinet.
All power-limited circuit wiring and nonpower-limited wiring must enter and exit the cabinet through different
knockouts. An example is shown below, although different knockouts may be used. The use of conduit is
optional for power-limited wiring. 

AC Primary Power

Wiring

(Nonpower-limited)

Run through either
knockout at the top

left corner.

Output Circuit

Wiring

(Power-limited)

Run through either

knockout  on the

right side.

Battery Storage Space - 12.2cmH x 38cmW x 10cmD

For further assistance, please contact the AlarmSaf Technical Service Department.

Reviews: