background image

1. Note the positions of the configuration jumpers on the back panel of the enclosure and

remove all jumpers.  Remove any terminal strips with wiring connected.

2. If the enclosure is installed in a rack, remove the four mounting screws and carefully slide the

unit out of the rack.

3. Remove the six screws holding the enclosure’s top cover in place and remove the top cover.
4. Remove the four 6-32 nuts holding the battery clamp in place (see Figure 4.1.2.1) and remove

the battery clamp, taking care to not damage or disconnect any wiring.

5. If replacing existing batteries, carefully lift each battery, disconnect the fast-on connectors

from the battery, and remove the battery from the enclosure

NOTE - When replacing the batteries, ALL of the batteries in the enclosure should be
replaced at the same time.  Ensure the new batteries are all of the same voltage and
AH capacity.

Figure 4.1.2.2

6. Connect and install new batteries, one at a time, as shown in F igure 4.1.2.2.
7. Carefully replace the battery clamp over the battery set.  Route the wiring through the slots,

ensuring that no wiring is stressed, pinched, or disconnected.

8. Resecure the clamp with the four 6-32 nuts removed in Step 4.
9. Replace top cover and secure with the six screws removed in Step 3.
10. Carefully replace unit into rack as described in Section 4.1.1 and reconnect all terminal strips

and configuration jumpers.

Rack Mount Battery Enclosure Installation Instructions
5/27/2009, 11:42:41 AM

52-342 Rev A.01

Page 8 of 14

AlarmSaf

 65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com

Summary of Contents for RMBE Series

Page 1: ...RMBE Series Rack Mount Battery Enclosure Operating and Installation Instructions 52 342 Rev A 01...

Page 2: ...working about the premesis by falling objects by customers by building vibration and by similar causes NOTICE This equipment is not intended for use within the patient care areas of a Health Care Faci...

Page 3: ...the RMBE Series 9 4 2 Wiring 7 4 1 Mounting 7 4 Installation 6 3 2 Terminal Descriptions 5 3 1 Electrical Ratings and Specifications 5 3 System Overview 5 2 Applicable Standards Documents 4 1 Introduc...

Page 4: ...es total of four 7AH batteries Each individual battery is protected by an internal self resetting PTC Each battery set can be configured for either 12VDC or 24VDC When set for the same voltage the two...

Page 5: ...1050 AlarmSaf Product Use When installed in accordance with all standards listed in Section 2 of this document the RMBE battery enclosure provides single or dual battery backup for rack mount applica...

Page 6: ...V 12V Two separate outputs 24V 24V Two separate outputs 12V and 24V Two separate outputs 12V One single output or 24V One single output VOLTAGE SELECTION BATTERY CONNECT CAUTION ONLY ONE VOLTAGE SELEC...

Page 7: ...uipment installed The RMBE should be installed near the bottom of the rack to ensure rack stability Install batteries into the RMBE enclosure See Section 4 1 2 Ensure all back panel jumpers are remove...

Page 8: ...enclosure NOTE When replacing the batteries ALL of the batteries in the enclosure should be replaced at the same time Ensure the new batteries are all of the same voltage and AH capacity Figure 4 1 2...

Page 9: ...LTAGE SELECTION 4 2 2 Battery Connection Locate the terminal wiring blocks on the back panel of the unit and remove the terminal block from the header there are two locking screws one on either end of...

Page 10: ...CTION 5 1 1 1 Voltage Selection Jumpers For each battery set only ONE voltage selection jumper must be in place The back panel of the RMBE is labelled for the voltage selection options Each battery se...

Page 11: ...orrect Verify internal batteries are not damaged and that they are charged replace if necessary Discharged Bad Battery Ensure that all internal wiring of the RMBE is connected properly Internal wiring...

Page 12: ...ations 6 2 1 Ambient Temperature Range 0 C to 49 C 32 F to 120 F 6 2 2 Ambient Humidity 93 at 32 C 90 F maximum 6 2 3 BTU Output Not Applicable 6 3 Mechanical Specifications 6 3 1 Weight Approx 30 lbs...

Page 13: ...3 71 0 815 3 250 DETAIL A TYPICAL 4 PLCS DETAIL A 25 1875 1875 0 683 0 75 16 87 Rack Mount Battery Enclosure Installation Instructions 5 27 2009 11 42 41 AM 52 342 Rev A 01 Page 13 of 14 AlarmSaf 65A...

Page 14: ...erters allow multi voltage system backup with a single battery set DC DC Converter Voltage distribution providing on off control for the outputs Control can be from FAI an access control panel card re...

Reviews: