PAGE 12
PAGE 3
KEY ACT
(KEY ACTIVE OUTPUT)
THIS IS AN NPN TRANSISTOR OPEN COLLECTOR OUTPUT THAT SWITCHES TO
GROUND, (-) FOR 10 SECONDS WITH EACH KEY PRESS. THIS CAN BE USED TO
TURN ON A BUZZER, TURN ON LEDS OR OPERATE A LOW CURRENT RELAY.
THE RATING OF THIS OUTPUT IS LIMITED TO Ic MAX. 100 MA. SINK, Vc MAX. 24VDC.
DU ACT
(DURESS OUTPUT)
THIS IS AN NPN TRANSISTOR OPEN COLLECTOR OUTPUT THAT SWITCHES TO
GROUND, (-) AFTER THE DURESS CODE HAS BEEN ENTERED. THIS CAN BE USED
TO TRIGGER AN ALARM ZONE OR TURN ON A BUZZER. THE RATING OF THIS
OUTPUT IS LIMITED TO Ic MAX. 100MA. SINK, Vc MAX. 24VDC.
DOOR SENS
(DOOR POSITION SENSOR INPUT)
A NORMALLY-CLOSED MAGNETIC CONTACT CONNECTED TO THIS TERMINAL AND
GROUND, (-) WILL MONITOR THE POSITION OF THE DOOR.
THIS TERMINAL MUST
BE CONNECTED TO GROUND, (-) IF NOT USED.
THE FACTORY INSTALLED JUMPER
MUST BE REMOVED WHEN USING THIS FEATURE
THE DOOR POSITION SENSOR WILL PROVIDE THE FOLLOWING:
1.
DOOR AUTO RE-LOCK
THE KEYPAD WILL IMMEDIATELY RE-LOCK AFTER THE DOOR CLOSES AND BEFORE
THE END OF TIME PERIOD THAT HAS BEEN PROGRAMMED FOR OUTPUT 1.
THIS PREVENTS “TAILGATE” ENTRIES.
2.
DOOR FORCED OPEN ALARM
THE KEYPAD WILL GENERATE A DOOR FORCED OPEN ALARM INSTANTLY IF THE
DOOR IS FORCED OPEN WITHOUT A VALID USER ENTRY CODE OR EGRESS
INPUT. THE ALARM WILL LAST FOR 60 SECONDS AND CAN BE TURNED OFF WITH
ONE OF THE USER CODES IN GROUP 1 AT ANYTIME.
3.
DOOR PROPPED OPEN ALARM
IF THE DOOR IS LEFT OPEN LONGER THAN THE PRE-SET TIME THE KEYPAD WILL
GENERATE A DOOR PROPPED OPEN ALARM UNTIL THE DOOR IS CLOSED. THE
DOOR OPEN TIME IS PROGRAMMABLE FROM 1 TO 999 SECONDS.
4.
INTER-LOCK CONTROL
THE INTER-LOCK CONTROL OUTPUT GOES TO GROUND, (-) WHEN THE DOOR IS
OPEN IN ORDER TO DISABLE THE SECOND KEYPAD IN THE INTER-LOCK SYSTEM.
O/P 1 INHIB.
(OUTPUT 1 INHIBIT)
THIS IS A NORMALLY-OPEN INPUT TERMINAL WHICH IS USED IN A CROSS WIRE
CONNECTION IN AN INTER-LOCK APPLICATION.
INT. LOCK
( INTER-LOCK CONTROL OUTPUT)
THIS IS AN NPN TRANSISTOR OPEN COLLECTOR OUTPUT THAT SWITCHES TO
GROUND, (-) FOR 5 SECONDS AFTER ENTERING A VALID USER CODE. USE THIS
OUTPUT TO CONTROL THE SECOND KEYPAD IN A “MANTRAP” APPLICATION.
A “MANTRAP” SYSTEM IS A TWO DOOR SYSTEM THAT ALLOWS ONLY ONE DOOR
TO OPEN AT A TIME. THIS PREVENTS ACCESS THRU DOOR 2 WHILE DOOR 1 IS
OPEN. ACCESS THRU DOOR 2 IS ALLOWED WHEN DOOR 1 IS CLOSED.
N.C TAMPER
THIS CONTACT IS NORMALLY-CLOSED WHILE THE KEYPAD IS SECURE TO THE BACK
BOX. WHEN THE KEYPAD IS SEPARATED FROM THE BACK BOX THE CONTACTS
OPEN. CONNECT THESE NORMALLY-CLOSED CONTACTS TO THE PANIC INPUT
OF AN ALARM PANEL IF REQUIRED.
DURESS OUTPUT
OUTPUT 2 APPLICATIONS
The Duress Output will switch to ground, (-), when the Duress Code is entered. This output can be
used to turn on a LED or piezo buzzer. This output can be connected to a 24 hour zone of an alarm
system. Only one connection option is recommended. See page 7 for details.
SHUNTING OF A N/C
PROTECTIVE ZONE
ARMING AND DISARMING
ALARM PANEL
TO ALARM PANEL
PROTECIVE ZONE
Use the n/o output contact of Output 2 to shunt a N/C protective zone. Set the Keypad in Latching
Mode. See page 6 for Keypad programming Latching Mode.
ALARM PANEL
REMOTE
ARM-DISARM
TERMINALS
Use the N/O or N/C output contact of Output 2 to arm or disarm a control panel. Set the Keypad in
Momentary Mode. See page 6 for Keypad programming Momentary Mode.
CURRENT NOT TO
EXCEED 100 MA.