To exit the Program Mode press the        key.  Keypad exits the Program Mode and returns to

normal operation.

The Duress Code does not have to be programmed. The Keypad determines it automatically

when the first digit of the User Code is increased by 2 digits to operate the Duress Output.

For example: 

The User Code 1 is 1234 then the Duress Code is 3234. If the User Code 1 is    

5862 then the Duress Code is 7862. If the User Code 1 is 8262 the the Duress

Code is 0262. 

When the Duress Code is entered then Output 1 will be active for the length of time set in the

Momentary Mode and the Duress Output switches to ground, (-) and can only be turned off by

entering the User Code 1.  When the Keypad is programmed for Latching Mode then Output 1

and the Duress Output will remain on until turned off by entering User Code 1.

There is no Duress Code for Output 2.

The Keypad will not allow duplicate code numbers when using the Duress Code feature. 

For example:

If the User Code stored in the system is 5678 then the Duress Code will be

7678 then the Keypad will not accept User Code number 7678.

When the Keypad is programmed for 

Auto Entry 

mode the        key that follows the entered

Code Number is 

not 

required.  In this mode the User Code must be the same length as the

Installer Code and the code length can be from four to eight digits.

To program the Keypad for Auto Entry press the             keys then press the        key then

press the        key.  

The Keypad is now in the Auto Entry Mode.

When the Keypad is programmed for 

Manual 

mode the        key that follows the entered User

Code 

is 

required.  In this mode the User Code can be from 4 to 8 digits in length but all the

User Codes do not need the same number of digits.

To program the Keypad for Manual Mode press the             keys then press the        then press

the        key. 

The Keypad is now in the Manual Mode.

PAGE 8

PAGE 7

CODE ENTRY MODES       AUTO OR MANUAL

APPLICATION EXAMPLES

DURESS OUTPUT FUNCTION

TO EXIT THE PROGRAM MODE

8 2

#

8 2

1

0

#

#

#

USER OPERATING INSTRUCTIONS

OPERATING THE KEYPAD IN THE MANUAL MODE TO OPEN DOOR

Enter any of the programmed User Codes.  (

see page 5 for programming User Codes

)

then press the            key to open the door.

Yellow Led turns on for 1 second then turns off.

OPERATING THE KEYPAD IN THE AUTO ENTRY MODE TO OPEN DOOR

Enter the User Code which can be from 4 to 8 digits long.

Yellow Led turns on for 1 second then turns off.

X X X X X X X X

X X X X X X X X

#

*

BASIC WIRING DIAGRAM OF A MAGNETIC LOCK AND ELECTRIC DOOR STRIKE

MODEL KP-400

The Keypad must be in the Momentary Mode in order for the Magnetic Lock or the 

Electric Door Strike to function correctly.  Use the N/C relay contacts when connecting

a magnetic lock.

The 1N4004 diode must be connected to the Electric Door Strike as shown in the dia-

gram above to prevent arcing across the Keypad relay contacts.  The diode is not re-

quired when powering the Electric Door Strike on AC current.  Use the N/O Output when

operating the Electric Strike in the fail-secure mode.  Use the N/C Output when operat-

ing the Electric Strike in the fail-safe mode.

The negative terminal of the Magnetic Lock must be connected to the negative terminal

of the power supply.

To avoid electrostatic discharge from interfering with the operation of the Keypad al-

12 OR 24

VOLT

AC OR DC

POWER SUPPLY

USE N/O 

CONTACTS

OR REQUEST

TO EXIT

STATION

MODEL TS-2

SHOWN

ELECTRIC

STRIKE WIRING
USE N/O RELAY

CONTACT FOR

FAIL-SECURE

USE N/C RELAY

CONTACT FOR

FAIL-SAFE

MAGNETIC LOCK

OR

ELECTRIC STRIKE

CATHODE

AC CAN ONLY BE

USED WITH AC

ELECTRIC STRIKES

Summary of Contents for KP-400

Page 1: ...AS DIE CAST METAL KEYS WITH AUDIBLE AND VISUAL KEY PRESS TWO PROGRAMMABLE S P D T RELAY OUTPUTS DOOR PROP OPEN ALARM DOOR FORCED OPEN ALARM BUILT IN TAMPER SWITCH BUILT IN BUZZER REQUEST TO EXIT INPUT...

Page 2: ...OCKS FOR 30 SECONDS RELAYS CAN BE SET FOR MOMENTARY OR LATCHING MODE ADJUSTABLE RELAY ON TIME FROM 1 TO 999 SECONDS KEYPAD BEEPER CAN BE SILENCED IF REQUIRED KEYPAD CAN BE PROGRAMMED FOR OUTPUT ANNUNC...

Page 3: ...OLS CORPORATION 19 BRANDYWINE DRIVE P O BOX 280 DEER PARK NY 11729 WWW ALARMCONTROLS COM SELF CONTAINED DIGITAL VANDAL RESISTANT WEATHERPROOF ACCESS CONTROL KEYPAD MODEL KP 400 OPERATING INSTRUCTIONS...

Page 4: ...S AC DC AUTO VOLTAGE SENSING ACTIVE CURRENT DRAW 100 MA MAX 12 V 120 MA MAX 24 V IDLE CURRENT DRAW 10 MA MAX 12 V 22 MA MAX 24 V OUTPUT 1 CONTACT RATING 5A 28 VDC OUTPUT 2 CONTACT RATING 1A 28 VDC REL...

Page 5: ...ER CODE MULTIPLE REQUEST TO EXIT STATIONS CAN BE CONNECTED IN PARALLEL TO THESE TERMINALS LED INDICATORS RED ON WHEN OUTPUT 2 IS ACTIVE GREEN ON WHEN OUTPUT 1 IS ACTIVE YELLOW MONITORS POWER DRY CONTA...

Page 6: ...1 TO 999 SECONDS 4 INTER LOCK CONTROL THE INTER LOCK CONTROL OUTPUT GOES TO GROUND WHEN THE DOOR IS OPEN IN ORDER TO DISABLE THE SECOND KEYPAD IN THE INTER LOCK SYSTEM O P 1 INHIB OUTPUT 1 INHIBIT TH...

Page 7: ...2 BEEPS SUCCESSFUL CODE ENTRY 5 FLASHES 5 BEEPS FAULTY CODE ENTRY CONTINUOUS FLASHING CONTINUOUS TONE DAP JUMPER NOT REPLACED CONTINUOUS FLASHING NONE 1 FLASH IN 2 SEC INTERVAL NONE 1 LONG BEEP OUTPU...

Page 8: ...LOWED To activate Keypad Initiation Mode enter then press the key The Yellow Led will flash twice and you will hear two beeps You are now in Keypad Initiation Mode 8 9 0 1 STEP 3 ENTERING THE USER COD...

Page 9: ...D SILENT MODE To exit the Program Mode press the key The Keypad returns to normal operation The Keypad can be programmed with additional features by using the following op tions You have only 10 secon...

Page 10: ...need the same number of digits To program the Keypad for Manual Mode press the keys then press the then press the key The Keypad is now in the Manual Mode PAGE 8 PAGE 7 CODE ENTRY MODES AUTO OR MANUA...