Installation and Operating Manual (translation)
54
AL-KO EASYAIR
®
IMPORTANT
The specified values must be adhered to, otherwise the plate heat exchanger may be damaged.
NOTE
To remove stubborn dirt, cleaning agents can also be used (e.g. all-purpose cleaner, biode-
gradable).
It must then be rinsed using plenty of fresh water!
Do not use aluminium cleaners! These are acidic and attack the surface of the plate heat
exchanger.
8.4.4 Multi-leaf dampers
WARNING
Risk of crushing
When closing the multi-leaf damper, there is a risk of crushing injuries to the hands.
Do not reach into the damper when closing the multi-leaf damper.
Wear the personal protective equipment.
8.4.4.1 Maintenance
Inspect the multi-leaf dampers for soiling, damage and corrosion.
Check the mechanical function of the multi-leaf dampers.
Check the end position of the damper adjustings actuators and adjust, if necessary.
Lubricate the damper bearing and joints if necessary using appropriate lubricants.
8.4.4.2 Cleaning
Clean the multi-leaf dampers at regular intervals.
8.4.5 Droplet eliminator
WARNING
Risk of cuts
There is a risk of cutting injuries during cleaning and maintenance of the droplet eliminator!
Wear personal protective equipment (cut-proof gloves)!
8.4.5.1 Maintenance
The droplet eliminator can be pulled out laterally from the housing for maintenance purposes.
Inspect the droplet eliminator for soiling, damage and corrosion.
Check water drain and siphon of the drain tray and top up if necessary.
8.4.5.2 Cleaning
The droplet eliminator can be pulled out laterally from the housing for cleaning purposes.
Summary of Contents for EASYAIR RO-01
Page 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Page 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Page 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Page 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Page 74: ......
Page 75: ......