Specifications
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
3
2 Specifications
Table 2.1
Power supply
Supply voltage
24 (19…30) V DC
Power consumption, max.
2.5 W
Galvanic isolation
none
Galvanic isolation against RS485 circuits
1000 V
Reverse polarity protection
yes
Appliance class
III
Network
Protocol
Modbus RTU/ASCII
Network mode
Master / Slave
Baud rate
9.6…115.2 kbit/s
Programming
Software
akYtec ALP 1.9 or newer
Interface
Micro-USB 2.0
Stack
dynamic
RAM
32 kB
ROM
128 kB
Network variable memory *
1020 Byte
Program cycle, min.
1 ms
Real-time clock
Accuracy
±3 s/day (25°C)
Backup, min.
1.5 years
Backup battery
CR1025
Mechanical
IP code
IP54 front / IP20 rear
Dimensions (with terminal block)
100 x 60 x 60 mm
Weight
approx. 150 g
EMC safety
EMC immunity
conforms to IEC 61326-1 / A1
EMC emission
conforms to EN 55011 / A1
* The limitation applies only to the slave mode, in which all network variables are automatically
declared as retain.
2.1
Environmental conditions
The module is designed for natural convection cooling. It should be taken into account when
choosing the installation site.
The following environment conditions must be observed:
−
clean, dry and controlled environment, low dust level
−
closed non-hazardous areas, free of corrosive or flammable gases
Table 2.2 Environmental conditions
Condition
Permissible range
Ambient temperature
-20…+55°C
Transportation and storage
-20…+55°C
Relative humidity
up to 80% (at +25°C, non-condensing)
Altitude
up to 2000 m above sea level