Status LEDs 

Messages 

Permanent:

 Compressor relay active.

Flashing:

 It must be activated, but it is not 

due to a parameter.

 

Defrost relay activated. 

Continuous cycle mode active. 

Permanent:

 Fan relay activated.

Flashing:

 It must be activated, but it is not 

due to a parameter.

 

Defrost ended by time. 

Energy saving mode active. 

Alarm active. 

Light relay activated. 

Auxiliary relay activated by key. 

Auxiliary relay indicating the unit's 
status (ON/OFF). 

Auxiliary active relay in pump 
down mode. 

Auxiliary relay activated per digital input. 

Auxiliary relay active in second defrost 
mode. 

Flashing:

  Alarm si alarm relay 

deactivated.

 

Permanent:

 HACCP function active.

Flashing:

 HACCP alarm stored not displayed.

 

ACCESS CODE:

Access code (password) request to enter to the programming menu or to change the set point.

DEFROST:

Indicates that a defrost is being performed.

THERMOSTAT CONTROL:

The thermostat control function is active.

EXTERNAL ALARM / SEVERE EXT. ALARM:

External alarm / severe external alarm activated by one of the digital inputs.

HIGH TEMP. ALARM / LOW TEMP. ALARM:

The temperature of probe 1 exceeds / is lower than the parameter programmed in Maximum alarm probe 1 / 
Minimum alarm probe 1.

L. PRESSURE ALARM:

The low pressure controller has triggered due an excessively low pressure in the low pressure circuit, adjustment 
stops.

ERROR PROBE 1, 2, or 3:

Probe 1, 2 or 3 broken (circuit open, crossed or temperature> 110 ºC or temp.<–55 ºC).

 

23

Auxiliary relay active copying relay status
for compressor.

English

Summary of Contents for PROPlus

Page 1: ...ico PROPlus Servicios con desescarche trif sico PROPlus Services with three phase defrost Services avec d givrage triphas Electronic Panel Tableau lectronique PROPlus E GB F 1564H331 Ed 02 Gu a r pida...

Page 2: ...influencias t rmicas ajenas a la temperatura que se desea medir o controlar Desconectar siempre la alimentaci n para realizar el conexionado El circuito de alimentaci n debe estar provisto de un inter...

Page 3: ...bajandoen l Conexi n de interruptor general y protecci n diferencial exterior al cuadro el ctrico seg n el reglamento electrot cnico debajatensi n Verificaciones antes de la puesta en marcha del cuadr...

Page 4: ...3 Seguidamente conectar los cables de alimentaci n trif sica al magnetot rmico F1 y hacer los puentes indicados en el esquema de conexi n Colocar las bridas seg n la figura 4 prestando especial atenci...

Page 5: ...L2 4 T2 5 L3 6 T3 13 NO 14 NO A1 A2 K1 FM F1 140 140 J I E Fig 2 Fig 4 Fig 5 Fig 3 Al montar el frontal prestar atenci n a que los cables no toquen la placa electr nica Utilizar las bridas suministrad...

Page 6: ...La funci n de la salida del rel auxiliar bornes 40 y 41 es configurable ver p g 24 ATENCI N Asegurese de desconectar la alimentaci n del equipo antes de manipular el equipo diversas zonas pueden tener...

Page 7: ...vera Polaridad entrada 2 Normalmente abierto Configuraci n rel AUX Recogida de gas Configuraci n Configuraci n Configuraci n 26 26 25 25 27 27 27 12 22 2 14 4 A 21 11 1 ALTA BAJA ALCO RANCO 26 25 B C...

Page 8: ...ulsando durante 5 segundos permite editar ladescripci ndelequipo Activa o desactiva el rel de luces Bornes 38 y 39 Esta funci n permanece activa aunque el equipo est en modo m Pulsando durante 5 segun...

Page 9: ...vado Permanente Funci n de HACCP activa Intermitente Alarma HACCP almacenada no visualizada C DIGO DE ACCESO Petici n de c digo de acceso Password para entrar en el men de programaci n o para variar e...

Page 10: ...ar id neo q Sondas conectadas Escoger la opci n adecuada en funci n del n de sondas conectadas Sonda 1 Si dispone de una sola sonda de control El desescarche finalizar por tiempo Sondas 1 y 2 Si dispo...

Page 11: ...G en S3 La sonda de control de temperatura alarmas y HACCP Sonda 1 se conecta en la entrada S1 y la sonda de registro de temperatura Sonda 3 en la entrada S3 Si la sonda 3 se configura como 2 desescar...

Page 12: ...s 0 estara siempre en marcha min 0 5 255 Parar el compresor al abrir la puerta Requiere entrada digital configurada como contacto puerta No Descripci n Unidades Min Def Max Tipo de desescarche Resiste...

Page 13: ...s al recibir alimentaci n el ctrica min 0 0 255 Retardo de alarmas despu s de un desescarche min 0 0 255 Retardo de alarmas tras el cierre de la puerta min 0 0 255 Retardo de alarmas tras la apertura...

Page 14: ...Des Duraci n de la recogida de gas Seg 1 30 1800 Retardo conexi n recogida Seg 0 60 60 Control del REL AUXILIAR Descripci n Unidades Min Def Max C digo de acceso Password a par metros y punto de ajust...

Page 15: ...0 320 Duraci ndelahorrodeenerg a h 0 0 24 CICLO CONT NUO AHORRO DE ENERG A Descripci n Unidades Min Def Max Retardo para el registro de un evento HACCP despu s de una alarma de temperatura 0 Registro...

Page 16: ...measure or control Always disconnect the power supply to do the wiring The power supply circuit should have a main switch and residual current protection outside the panel according to 2 2 R E B T The...

Page 17: ...nt Close the panel when your are not working on it Main switch connection and residual current protection outside the electrical panel according to low voltage electrotechnical regulations Checks befo...

Page 18: ...ase power supply cables to F1 circuit breaker and make the connections shown in the wiring diagram Install the flanges according to figure 4 making sure the cables do not touch the electronic board wh...

Page 19: ...1 3 L2 4 T2 5 L3 6 T3 13 NO 14 NO A1 A2 K1 FM F1 140 140 J I E Fig 2 Fig 4 Fig 5 Fig 3 When assembling the front part make sure the cables do not touch the electronic board Use the supplied flanges 19...

Page 20: ...equipment s power supply before handling it as different areas may be energised IMPORTANT The recommended currents and powers are the maximum working currents and powers The function of each probe de...

Page 21: ...pen Aux relay configuration Pump down control Configuraci n Configuraci n Configuraci n 26 26 25 25 27 27 27 12 22 2 14 4 A 21 11 1 HIGH LOW ALCO RANCO 26 25 B C DANFOS PENN Input 1 configuration Low...

Page 22: ...activates or deactivates the cold room light terminals 38 and 39 This function stays active although the unit is in the m mode Pressing it for 5 seconds activates or deactivatesthedefrost Pressing it...

Page 23: ...deactivated Permanent HACCP function active Flashing HACCP alarm stored not displayed ACCESS CODE Accesscode password requesttoentertotheprogrammingmenuortochangethesetpoint DEFROST Indicatesthatadefr...

Page 24: ...on according to the no of probes connected Sensor 1 If it has just one control probe Defrost will end by time Sensor 1 and 2 If it has two probes a control probe and another one for defrost evaporator...

Page 25: ...f the S2 input is not configurable TEM at S1 REG at S3 The temperature control alarms and HACCP probe Probe 1 is connected to the S1 input and the temperature data logger probe Probe 3 to the S3 input...

Page 26: ...is 0 it will always be running min 0 5 255 Stop when opening door It requires a digital input configured as door contact No Description Units Min Def Max Defrost type Electrical heater Hot gas bypass...

Page 27: ...rm delay min 0 30 255 Start up alarm delay min 0 0 255 Alarm delay after defrost min 0 0 255 On Off door alarm delay min 0 0 255 Off On door alarm delay min 0 0 255 Alarm relay after key After pressin...

Page 28: ...robe 2 Probe 3 Dis Pump down duration Sec 1 30 1800 Pump down On delay Sec 0 60 60 AUXILIARY RELAY control Description Units Min Def Max Access password to parameters and set point 00 00 99 Password t...

Page 29: ...0 0 0 320 Energy saving duration h 0 0 24 Description Units Min Def Max HACCP alarm delay after a temperature alarm 0 Events log deactivated min 0 1 255 HACCP Description Units Min Def Max Language Es...

Page 30: ...re que vous souhaitez mesurer ou contr ler D branchez toujours l alimentation pour faire la connexion Le circuit d alimentation doit tre muni d un interrupteur g n ral et d une protection diff rentiel...

Page 31: ...us Connexion de l interrupteur g n ral ou de la protection diff rentielle ext rieure au tableau lectrique selon le r glement lectrotechnique de basse tension V rifications avant la mise en marche du t...

Page 32: ...et 13 Puis connectez les c bles d alimentation triphas e au magn tothermique F1 et faites les ponts indiqu s dans le sch ma de connexion Placez les brides selon la figure 4 en faisant particuli remen...

Page 33: ...5 L3 6 T3 13 NO 14 NO A1 A2 K1 FM F1 Fig 2 Fig 4 Fig 5 140 140 Fig 3 Lors du montage de la fa ade faites attention ce que les c bles ne touchent pas la plaque lectronique Utilisez les brides fournies...

Page 34: ...tation de l quipement avant de manipuler l quipement diff renteszonespeuvent tresoustension IMPORTANT Les intensit s et puissance indiqu es sont les valeurs maximales de travail autoris es La fonction...

Page 35: ...relai AUX Controle mise au vide Configuration Configuration Configuration 26 26 25 25 27 27 27 12 22 2 14 4 A 21 11 1 ALCO RANCO 26 25 B C DANFOS PENN Configuration entr e 1 Entr e basse pression Pol...

Page 36: ...econdes pour diter la descriptiondel quipement Active ou d sactive la lumi re de la chambre Bornes 38 et 39 Cette fonction reste active m me si l quipement est en mode m Appuyez pendant 5 secondes pou...

Page 37: ...rme d sactiv Permanent Fonction de HACCP active Clignotant Alarme HACCP stock e non visualis e CODE D ACC S Demande de code d acc s Password pour entrer dans le menu de programmation ou pour modifier...

Page 38: ...Sondes connect es Choisirl optioncorrecteenfonctiondunombredesondesconnect es Sonde1 Sivousdisposezd uneseulesondedecontr le Led givragetermineralorsqueladur esera coul e Sondes1et2 Sivousdisposezded...

Page 39: ...de contr le de temp rature les alarmes et HACCP Sonde 1 est connect e sur l entr eS1etlasondederegistredetemp rature Sonde3 surl entr eS3 Silasonde3estconfigur ecomme2d givrage leregistreestd sactiv T...

Page 40: ...dommagee S il est sur 0 il sera toujours en marche min 0 5 255 Arr ter lors ouvert porte le compresseur N cessite une entr e num rique configur e comme contact de porte No Description Unit s Min Def M...

Page 41: ...a la conexion min 0 0 255 Retard fin d givrage min 0 0 255 Retard On Off porte min 0 0 255 Retard Off On porte min 0 0 255 Alarme relai apr s touche Alarme en mode muet Relie D connect Con Contr le de...

Page 42: ...ctiv e Sonde 2 Sonde 3 D s Duree de la mise au vide Sec 1 30 1800 Retard dem mise au vide Sec 0 60 60 Fonction du RELAISAUXILIAIRE TAT G N RAL Description Unit s Min Def Max Mot de passe Password 00 0...

Page 43: ...e epargne energetique h 0 0 24 CYCLE CONTINU CONOMIE D NERGIE Description Unit s Min Def Max Retard alarme HACCP apr s une alarme de temp rature 0 Registre d v nements d sactiv min 0 1 255 HACCP Descr...

Page 44: ...i n actualizada en nuestra web WereservetherighttosupplymaterialsslightlydifferenttothosedescribedinourDataSheets Updatedinformationinourwebsite Nous nous r servons le droit de fournir des mat riels p...

Reviews: