6.- Quick configuration
The quick configuration menu allows the unit to be configured for the most common applications. Press the key
for 5 seconds to access it.
If the access code is activated, a 2 digit code is requested (See p. 15), if the code entered is not correct the unit will
not enter programming.
If more specific configuration is required use the advanced configuration menu (see p. 17)
After 20 seconds without touching any key, the unit returns to the previous level without saving changes or it will
exit programming.
Function of the keys in programming
SP: Set point
It sets the coldroom's working temperature (see p. 9)
Ÿ
Minimum: –45.0 *
Ÿ
Maximum: 99 *
*(Depends on the bottom/top locking of the set point).
d0: Defrost frequency
Time that must elapse between the starting of each defrost (see p. 11)
d1: Maximum defrost duration
The defrost will end after this time has elapsed since it started.
F3: Fan status during defrost
It defines the status of the fans during defrost.
0=
Stopped
1=
Running
A1: Maximum alarm probe 1
Defines the temperature at which the maximum alarm will be triggered. Only affects probe 1.
Ÿ
Minimum: –45.0 *
Ÿ
Maximum: 99 *
*(Depends on the bottom/top locking of the set point).
A2: Minimum alarm probe 1
Defines the temperature at which the minimum alarm will be triggered. Only affects probe 1.
Ÿ
Minimum: –45.0 *
Ÿ
Maximum: 99 *
*(Depends on the bottom/top locking of the set point).
P26: Stoppage owing to pump down
It defines whether this function is active
Ÿ
0
= Without pump down
Ÿ
1
= With pump down
(see p. 13)
Passes back to the previous parameter or
decreases the value of the parameter.
Passes on to the next parameter or increases the
value of the parameter.
Accesses the selected parameter or accepts the
value.
Allows exiting a parameter without saving the
changes or exiting programming.