OFF

No alarms

Detector turned off

1st set of levels activated

ON

Alarm / Pre-Alarm activated

Standard operation

2nd set of levels activated

Flashing*

Alarm / Pre-Alarm saved

Standard operation, acoustic 

alarm disabled

MAINTENANCE mode 

activated

Flash*

Detector error

Detector in initialisation 

process

SET HOLD mode activated

Pre-Alarm

Alarm

Sensor error 

Intermittent

sound

Bi-tonal 

sound

3 tones 

every 2 minutes

Description

Refrigerant gas detector, which can be used in independent operation or connected to alarm stations AKOCam, AKOAlarm and AKOGas. 

Independent detector:

 The detector makes a certain warning sound in the event of an Alarm, Pre-Alarm or sensor error and the red indicator lights up (See operation section).

Detector connected to the alarm station: 

The detector notifies the station of its status (Alarm, Pre-Alarm or sensor error) and the station notifies the alarm through sound and indicators (for 

further information consult the station's manual). 

Pre-alarm jumper

Configuration push-button

Connection strip

Delay and alarm

levels configuration

Pre-alarm enabled

Pre-alarm disabled

Alarm delay

C

C

NC

NC

NO

NO

Gas 

Alarm

Tr

Tr

Tr+

 

Tr+

 

Gnd

Gnd

RS485

RS485

Alarm

Alarm

15V

15V

S

S

Gnd

Gnd

Red: Alarms

Green:

Operation

Mute 

push-button

Blue: Operating 

mode

Operation

Mute push-button

In the event of an Alarm or Pre-Alarm in process, any push-button press silences the Alarm/Pre-Alarm tone. 
Any push-button press deletes saved alarms.

Medium press

 (between 3 and 9 sec.): It activates or deactivates the SET-HOLD mode. Should there be a sensor error, reset the detector.

Long press

 (> 9 sec.): It activates or deactivates the MAINTENANCE mode. Should there be a sensor error, reset the detector.

Configuration

In this mode the acoustic alarm can be activated / deactivated or the detector can be returned to factory settings. 
To activate it:

1.- Disconnect the power supply, reconnect it and press the “CONFIGURATION” push-button 5 times within 2 minutes; the detector will emit a confirmation beep and the blue indicator will show the 

status of the acoustic alarm: 

ON:

 Acoustic alarm enabled / 

Flashing:

 Acoustic alarm disabled.

2.- Press the Mute push-button to enable / disable the acoustic alarm.
3.- Press the “CONFIGURATION” push-button for 5 seconds to save the changes and exit the configuration mode; the detector will make 5 short beeps.

Optionally, you can return the detector to its factory settings. To do so, press the “CONFIGURATION” push-button 5 times before step 3.

Pre-alarm jumper

Allows for Pre-alarm detection to be enabled / disabled. Before using this option, ensure that regulations allow for two alarm levels.

SET-HOLD mode

Prevents false alarms when charging or cleaning the chambers. While this mode is activated, pre-alarms will not signal and alarms will signal as pre-alarms when faced with all effects (sound, relay 
activation and signalling). This mode will remain active for a maximum of 5 hours, then will deactivate automatically.

Maintenance mode

Disables gas pre-alarms and alarms for 1 hour for maintenance tasks. While this mode is activated, no gas pre-alarm or alarm will sound.

*

Flashing:

  0.5 s ON / 0.5 s ON  / 

Flash:

 0.1 s ON / 0.8 s OFF 

GASES DETECTED

DEFAULT LEVELS

SECOND SET OF LEVELS

PRE-ALARM

ALARM

PRE-ALARM

ALARM

R-32, R-454A, R-454C, R-454C, R-455A, R-1234YF

1000 ppm

1500 ppm

2000 ppm

4000 ppm

Audible alarm

Alarm relay

Pre-Alarm

Alarm

Sensor error 

C

NC

NO

C

NC

NO

C

NC

NO

Connection to alarm station 

Alarm station

15V

In

Gnd

Input x

GAS

Independent operation 

12 - 30 Vdc

Without 

delay

ON

1

2

ON

1

2

180 s

Alarm levels

By 

default

ON

1

2

ON

1

2

2nd set 

of levels

Always disconnect the power supply to do the wiring.
The wiring between the detector/transmitter and the station should 

NEVER

 be installed in 

a conduit together with power, control or supply cables. 
Cables for wiring the relay contact should have an adequate section depending on the unit 
to be connected.
Certain  international  standards  maintain  that  the  power  supply  of  the  alarm  should 
originate from a different circuit to that used by the refrigeration and ventilation system. 

Please ensure that you comply with current local regulations.

Indicators

Wiring

Second alarm set is recommended for R-32 and R-1234YF 
refrigerants.