Subject to technical amendments without prior notice | 83058800fUK | ait-deutschland GmbH
Accessories for heat pump type
WR 2.1-1/3 8kW
WR 2.1-1/3 12kW
Air/water 8 kW output-controlled | Air/water 12 kW output-controlled
• yes – no
• | –
– | •
Air/water Dual output-controlled
• yes – no
– | –
– | –
Installation location
Room temperature
min. | max.
°C
5 | 35
5 | 35
Relative humidity
%
60
60
Sound
Sound pressure level at 1 m distance
inside
dB(A)
–
–
Sound power level
inside
dB(A)
–
–
Heating circuit
Flow rate: minimum | maximum (see heat pump for pipe dimensioning)
l/h | l/h
600 | 1200
600 | 1900
Free pressing | Pressure loss | Flow rate
bar | bar | l/h
0,9 | – | 1200
0,68 | – | 1900
Volume flow: minimum | nominal analogous to A7W35 (partial load operation) | maximum
l/h
600 | 600 | 1200
600 | 850 | 1900
Max. allowable operating pressure
bar
3
3
Circulation pump control range
min. I max.
l/h
600 ı 1200
600 ı 1900
General unit data
Total weight
kg
5,3
5,3
Weight of individual components
kg | kg | kg
– | – | –
– | – | –
Electrics
Voltage code | all-pole fuse protection for heat pump *)**)
1 phase
… | A 1~N/PE/230V/50Hz | B16
– | –
Voltage code | all-pole fuse protection for heat pump *)**)
3 phases
… | A 3~N/PE/400V/50Hz | B16
3~N/PE/400V/50Hz | B16
Voltage code | Control voltage fuse protection **)
… | A 1~N/PE/230V/50Hz | B10
1~N/PE/230V/50Hz | B10
Voltage code | Electric heating element fuse protection **)
1 phase
… | A
– | –
– | –
Voltage code | Electric heating element fuse protection **)
3 phases
… | A
– | –
– | –
Degree of protection
IP
20
20
Residual current circuit breaker
if required
type
B
B
Electric heating element output
3 | 2 | 1 phase
kW | kW | kW
– | – | –
– | – | –
Circulation pump power consumption, heating circuit
min. I max.
W
4 | 75
4 | 75
Other unit information
Safety valve Heating circuit | Response pressure
included in scope of supply: • yes – no | bar
– | –
– | –
Buffer tank | Volume
included in scope of supply: • yes – no | l
– | –
– | –
Diaphragm expansion vessel Heating circuit | Volume | Prepressure
incl. in scope of supply: • yes – no | l | bar
– | – | –
– | – | –
Overflow valve | Changeover valve, heating -Domestic hot water
integrated: • yes – no
– | –
– | –
Vibration decoupling, Heating circuit | Heat source
included in scope of supply or integrated: • yes – no
–
–
Controller | Heat quantity recording | Extension board
included in scope of supply or integrated: • yes – no
• | • | –
• | • | –
813317a
813317a
*) compressor only, **) note local regulations
Bezeichnung:
Datei: 823281 Freie Pressung WR 2.1-1/3
Änd./ÄM/Ersteller/Datum
- /PEP 012-2016 / Döring / 17.07.2017
823281
Seite: 1/1
Zeichnungsnummer:
Legende:
“”
Volumenstrom Heizwasser in m
3
/h
∆pmax
maximale freie Pressung
Freie Pressung WR 2.1-1/3
823281
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
0,0
0,5
1,0
1,5
2,0
2,5
3,0
Δ
pm
ax
[bar
]
Δ
pmax
Δ
p
“ ” [m
3
/h]
Key: UK823281
Key: UK823281
“”
“”
Hot water flow rate
Hot water flow rate
∆pmax
∆pmax
Maximum free pressing
Maximum free pressing
Technical data / Scope of supply
Free pressing
Summary of Contents for WR 2.1
Page 22: ...22 Subject to technical amendments without prior notice 83058800fUK ait deutschland GmbH ...
Page 23: ...23 Subject to technical amendments without prior notice 83058800fUK ait deutschland GmbH ...
Page 24: ...ait deutschland GmbH Industriestraße 3 D 95359 Kasendorf www ait deutschland eu UK ...