10
Procedure:
1.
Remove the sleeve from the AC cable by 200 mm.
2.
Strip the insulation of L1, L2. L3, N and the grounding conductor (PE) by
14 mm.
3.
Conductors L, N and the grounding conductor (PE) should each be fitted
with appropriate size ferrules.
4.
Insert the conductors according to
1.5 Nm ±0.3 Nm torque.
5.
Place the contact insert into the sleeve housing.
6.
Tighten the four screws on the front side of the contact insert with 1.5 Nm
±0.3 Nm torque.
7.
Secure the sleeve housing with a cable gland.
Figure 3
AC conductors connection
NOTICE
Risk of equipment damage
•
Ensure that L1, L2, L3, N and PE connections are done correctly.
•
AC plug openings are labelled 1, 2, 3, 4 and ground, however L1
conductor must be inserted into opening 4, L2 conductor into opening 3
and L3 conductor into opening 2, N into opening 1.