CONFIGURATION
CONFIGURATION MODES WITH LUTRON SYSTEMS
Depending on the existence or absence of Airzone thermostats in the zones, there are two available configurations.
Regardless of which thermostats are used, the HomeWorks QS system will have full control of the HVAC zones from the keypads,
time clocks and the Lutron Connect App.
Configuration with Lutron Palladiom thermostat to control the HVAC zone
When a Lutron Palladiom thermostat is used to control an HVAC zone, there are two integration commands used. First,
depending on the type of HVAC system, the Airzone-Lutron interface will use
DEVICE
commands
to read the current
temperature from the Palladiom thermostat. Second, the Airzone-Lutron interface will use
HVAC commands
for control of the
set-point temperature, operating mode and fan speed.
The
Integration IDs
of the
DEVICE
and
HVAC
commands
must follow the rules below:
When the system uses Lutron Palladiom thermostats, it uses
DEVICE commands
to read the room temperature with the
Integration
ID: 2XXYY
format, where XX stands for the system’s number and YY stands for the zone’s number.
XX
01 for Airzone system 1, 02 for Airzone system 2... Up to 32 Airzone systems.
YY
01 for Airzone zone 1, 02 for Airzone zone 2... Up to 32 Airzone zones per system (based on the type of the system).
Example
: A Palladiom thermostat DEVICE Integration ID for the Airzone system 1 and for zone 1 will be 20101.
The Airzone system uses
HVAC Integration IDs
to control the set-point temperature, operating mode and fan speeds using the
Integration
ID: 1XXYY
format, where XX stands for the system’s number and YY stands for the HVAC zone’s number.
XX
01 for Airzone system 1, 02 for Airzone system 2... Up to 32 Airzone systems.
YY
01 for Airzone zone 1, 02 for Airzone zone 2... Up to 32 Airzone zones per system (based on the type of the system).
Example
: A HVAC Integration ID for the Airzone system 1 and for the zone 2 will be 10102.
Configuration with Airzone thermostat
When an Airzone thermostat is used to control an HVAC zone,
HVAC integration commands
are used for control of set-point
temperature, operating mode and fan speed.
The Airzone system uses
HVAC Integration
IDs
to identify and to associate the system and the HVAC zone with the
Integration
ID: 1XXYY
format, where XX stands for the system’s number and YY stands for the HVAC zone’s number.
XX
01 for Airzone system 1, 02 for Airzone system 2... Up to 32 Airzone systems.
YY
01 for Airzone zone 1, 02 for Airzone zone 2... Up to 32 Airzone zones per system (based on the type of the system).
Example
: A HVAC Integration ID for the Airzone system 1 and for the zone 3 will be 10103.