Model
AWAU-YCV150-H11
Outdoor coil
Number of rows
2
Tube pitch (a)×row pitch (b)
mm
21*18.186
Fin spacing
mm
1.40
Fin type (code)
Corrugated
Fin coating type
Optional
Hydrophilic aluminum
Salt spray test duration
Hour
500
Tube outside dia. and type
Internal thread copper tube
mm
Ф7
Coil length×height
mm
970×1197
Number of circuits
7
Cabinet coating
Coating type
Powder Coating
Salt spray test duration
Hour
500
Sheet metal material
Hot zinc plate
Sheet metal thickness
mm
0.8
Control panel enclosure IP class
Standard
IP24
Outdoor air flow
m
3
/h
6500
Outdoor sound level (sound pressure level )
dB (A)
58
Outdoor sound level (sound power level )
dB (A)
69
Outdoor unit
Dimension (W*H*D)
mm
960/340/1250
Packing (W*H*D)
mm
1095×410×1400
Net weight
kg
99
Gross weight
kg
107
Refrigerant
Type
R410A
Charged volume
kg
3.8
Throttle type
EXV
Design pressure
MPa
4.15
Refrigerant piping
Liquid pipe
mm
9.52
Gas pipe
mm
19.05
Total pipe length
m
150
Max. pipe length
m
70
Max. Diff. indoor/outdoor unit
m
Max. Diff. indoor/indoor unit
m
10
Connectable indoor unit ratio
%
50%~130%
Maximum indoor units
Piece
8
Connection wiring
Power wiring
mm
2
16
Signal wiring
mm
2
Shield wire:(0.75-2)*2
Operation range
°C
Cooling: -5~48
Heating: -15~21
Nominal condition:
Indoor temperature (cooling): 27 DB(°C)/19 WB(°C), indoor temperature (heating): 20 DB(°C)/14.5 WB(°C).
Outdoor temperature (cooling): 35 DB(°C)/24 WB(°C), outdoor temperature (heating): 7 DB(°C)/6 WB(°C).
The data is measured with 7.5m equivalent pipe and 0m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
real time analyser calibrated sound intensity meter. It is a sound pressure noise level.