39
Outdoor unit PCB dipswitch setting (attention the different PCB version.)
■ Defined principles of dial switch:
BM1 puts emphasis on setting or debugging during the project, while BM2 during factory production.
①
BM1 introduction
13. Dip Switch Setting
Electric wiring and the application
BM1_1 Lock indoor quantity
[1] Lock indoor quantity
OFF Begin to search indoor
ON Stop searching indoor and lock quantity
BM1_2 Reserved
[2] Reserved
OFF Reserved (default)
ON Reserved
BM1_3 Fan selection
[3] Fan selection
OFF All AC
ON All DC
BM1_4 Priority selection for energy saving /
effect
[4]
Priority selection for energy saving /effect
OFF
Energy saving priority
ON
Effect priority
BM1_5 Indoor ON / OFF simultaneous
control
[5] Indoor ON / OFF simultaneous control
OFF
Every indoor unit can be controlled seperately
ON All the indoor units will simultaneous ON or OFF
BM1_6 Defrosting condition selection
[6] Defrosting condition selection
OFF
Not easy to frost area(default)
ON Easy to frost area
BM1_7 Defrosting level
[7] Defrosting level
OFF
Ordinary defrosting (default)
ON Strengthen defrosting (increase the defrositng time)
BM1_8 Silent operation selection
[8] Silent operation selection
OFF
Without silent operation(default)
ON Silent operation