5-1
PERFORMANCE DATA & PRESSURE CURVES
Service Manual - DUO Series
5. PERFORMANCE
DATA
5.1
DUO ALPHA (9+9):Room A + Room B
5.1.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
5.38 5.57 5.70 5.83 5.92
SC
3.65 3.81 3.96 4.06 4.13
PI
1.30 1.31 1.31 1.31 1.32
20
(1)
TC
5.20 5.48 5.65 5.79 5.91
SC
3.58 3.77 3.93 4.05 4.12
PI
1.42 1.42 1.43 1.43 1.44
25
TC
4.92 5.31 5.59 5.75 5.90
SC
3.49 3.70 3.90 4.02 4.09
PI
1.53 1.54 1.55 1.56 1.57
30
TC
4.60 5.01 5.41 5.61 5.77
SC
3.38 3.59 3.82 3.93 4.00
PI
1.65 1.68 1.69
1.70 1.72
35
TC
4.26 4.62
5.10
5.36 5.61
SC
3.21 3.44
3.73
3.84 3.91
PI
1.78 1.81
1.84
1.85 1.86
40
TC
3.87 4.22 4.60
5.03 5.29
SC
3.03 3.26 3.53 3.64 3.72
PI
1.92 1.95 1.98 2.01 2.03
46
TC
3.36 3.68 4.04 4.47 4.81
SC
2.79 2.99 3.22 3.33 3.40
PI
2.10 2.13 2.18 2.21 2.23
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
Summary of Contents for WNG12
Page 37: ...8 1 WIRING DIAGRAMS Service Manual DUO Series 8 WIRING DIAGRAMS 8 1 DUO 9 9 9 12...
Page 38: ...9 1 ELECTRICAL CONNECTIONS Service Manual DUO Series 9 ELECTRICAL CONNECTIONS 9 1 DUO 9 9 9 12...
Page 42: ...13 1 TROUBLESHOOTING Service Manual DUO Series 13 TROUBLESHOOTING...
Page 43: ...13 2 TROUBLESHOOTING Service Manual DUO Series...