background image

9

Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds with hands 
before fasten the flare nuts. (Refer to chart 19)
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.

CAUTION

Use frozen oil

Bend the pipe with thumb

min-radius 100m

Make the end straight

Chart 19

Chart 20

Chart 21

The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, 
first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts 
have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause 
malfunction later. So please expel the air out of the pipe with refrigerant (R-22) before connection.

Expel the air (refer to the

Expel The Air

) after connecting the refrigerant pipe with the indoor unit and the 

outdoor unit. Then fasten the nuts at the repair-points.

3)

4)

Notices For Bendable Pipe

Bend the connecting pipe of small wall thickness 

(

K

9.53mm)

 

Cut out a desired concave at the bending part of the insulating pipe.
Then expose the pipe (cover it with tapes after bending).
To prevent collapsing or deforming, please bend the pipe at its biggest radius.
Use bender to get a small radius pipes.

INSTALL THE CONNECTING PIPE

CAUTIONS

CAUTIONS

Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, 
and the number of the bends meet the following requirements:

The max height drop ......................................................................................................................20m
(If the height drop is more than 10m, you had better put the outdoor unit over above the indoor unit.)
The length of refrigerant pipe .........................................................................................less than 30m
The number of bends ........................................................................................................less than 15

CAUTIONS

CAUTIONS

Do not let air, dust, or other impurities fall in the pipe system during the time of installation.
The connecting pipe should not be installed until the indoor and outdoor units have been fixed already.
Keep the connecting pipe dry, and do not let moisture in during installation.

The Procedure of Connecting Pipes

The Procedure of Connecting Pipes

Measure the necessary length of the connecting pipe, and make it by the following way. (Refer to 

Connect The Pipes

for details)

1.

1) Connect the one-way valve restrictor in accessories to liquid tube assy,indoor unit at first (Note:only KN- 30/36/45) 
2) Connect the indoor unit,then the outdoor unit. 
   

Bend the tubing in proper way. Do not harm to them.

The bending angle should not exceed 90 .
Bending position is preferably in the middle of the bendable pipe. The larger the bending radius the better it is.
Do not bend the pipe more than three times.

K INST. MENU

Summary of Contents for KN-24SH

Page 1: ...OWNER S MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this owner s manual carefully before using the air conditioner and reserve this manual in case of further reference K INST MENU...

Page 2: ...N 3 OPERATION ATTENTION 4 TEMPORARY OPERATIONS 5 ADJUSTING AIR FLOW DIRECTION 5 HINTS FOR ECONOMICAL OPERATION 6 MAINTENANCE 6 PHENOMENA NOT CONCERNING MALFUNCTIONS 8 TROUBLES AND CAUSES concerning th...

Page 3: ...5 5 6 6 8 9 9 ADJUSTING AIR FLOW DIRECTION 10 1 POWER LOCATION INSTALLATION K INST MENU...

Page 4: ...2 CAUTION 3 c KN 27SH operation lamp timer indicator heat indicator power supply indicator K INST MENU...

Page 5: ...2 CAUTION 3 c KN 27SH operation lamp timer indicator heat indicator power supply indicator K INST MENU...

Page 6: ...4 NOTICE only cooling model without heating operation K INST MENU...

Page 7: ...atory HEAT and mandatory COOL can be selected through the TEMPORARY BUTTON on the air inlet grill control box of the indoor unit Once you push this button the air conditioner will run in such order ma...

Page 8: ...6 HINTS FOR ECONOMICAL OPERATION MAINTENANCE CAUTION METHOD FOR CLEANING AIR FILTER K INST MENU...

Page 9: ...7 MAINTENANCE CLEANING THE AIR OUTLET AND THE PANEL CAUTIONS MAINTENANCE IF YOU DO NOT PLAN TO USE THE UNIT FOR A LONG TIME THE MAINTENANCE OF THE OUTDOOR UNIT K INST MENU...

Page 10: ...8 8 RESTART AFTER A LONG TIME PHENOMENA NOT CONCERNING MALFUNCTIONS Fox each Mode including Power OFF and SB a Min time delay of 3min before Comp restarting excluding Deicing Mode K INST MENU...

Page 11: ...9 K INST MENU...

Page 12: ...PREPARATION 10 K INST MENU...

Page 13: ...INSTALLATION MANUAL For correct installation read this manual before starting installation This manual may be subject to change without notice for purpose of improvement K INST MENU...

Page 14: ...ATION INFORMATION 2 3 ATTACHED FITTINGS 3 4 INSTALLATION PLACE 4 5 INDOOR UNIT INSTALLATION 5 6 OUTDOOR UNIT INSTALLATION 8 7 INSTALL THE CONNECTING PIPE 9 8 CONNECT THE DRAIN PIPE 13 9 WIRING 15 10 T...

Page 15: ...ations on system turn off main power switch of the unit Electrical shock could cause personal injury This unit shall be installed in accordance with national wiring regulations If the supply cord is d...

Page 16: ...S FOR THE REMOTE CONTROLLER OPERATION 5 4 3 2 1 For any question contact your local dealer For power details of the air conditioner refer to the rating plate of the product for products like washing m...

Page 17: ...4 11 Wall conduit cover 1 10 Wall conduit 1 Protect Pipe Fittings 1 3 Installation pape board 4 13 Frame 1 12 Remote controller 1 Remote controller Its Frame 15 Alkaline dry batteries AM4 2 10 C H 2 1...

Page 18: ...d be extracted out easily There is no direct radiation from heaters There is enough room for installation and maintenance The air outlet and the air inlet are not impeded and can mot be reached by str...

Page 19: ...h of the installation hooks from the height of ceiling then cut off the unnecessary part c Please adjust the hexangular nuts on the four installation hooks evenly to ensure the balance of the body The...

Page 20: ...r installation Remove the installation paper board Please first guarantee the flatness and horizontal of ceiling when installing it Refer to the A a mentioned above for others a b c d CAUTIONS CAUTION...

Page 21: ...hat of the control box with corresponding terminators on the body respectively Relocate the air in grid in the procedure of reversed order Relocate the installation cover Malfunction described in Char...

Page 22: ...formance from being impeded by too little of air circulation that the same is applicable to the situation of an airtight room Leave open two of the three directions A B C MOVING AND INSTALLING MOVING...

Page 23: ...bend the pipe at its biggest radius Use bender to get a small radius pipes INSTALL THE CONNECTING PIPE CAUTIONS CAUTIONS Check whether the height drop between the indoor unit and outdoor unit the leng...

Page 24: ...f stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in fluent flow Be sure of no leakage by checking it with leak detector or soap water Cov...

Page 25: ...Turn anticlockwise the quadrangle of stop O value B to 45 for about 10 seconds and close the value stem of stop value B Check the leakage of all the joints on A B C and D After confirming of no leaka...

Page 26: ...cribed in the left chart Refer to Chart 28 ON operation Take off quadrangle cover clip the quadrangle head with a wrench and turn it anticlockwise to the end Then fasten the quadrangle cover OFF opera...

Page 27: ...as not to interfere other people or public Select the position where it will not be subject to snow drifts accumulation of leaves or other seasonal debris It is important that air flow for the outdoo...

Page 28: ...operation to avoid leakage Chart 32 3 3 Drain Elbow Installation Cooling Only Type Without Seal Drain elbow The base pan hole of outdoor unit The base pan of outdoor unit Seal Drain elbow Fit the sea...

Page 29: ...ed carefully after wiring covered with insulator tape do not twist two wiring together unless the joint is soldered well and proper length if necessary Generally The wiring attached to this air condit...

Page 30: ...INDOOR 5 CORE Cable RW 300 500 5X1 5mm2 5 CORE Cable YZW 300 500 5X1 5mm2 3 CORE Cable 3X1 5mm2 Note The cooling only type withoout the link listed by broken line KN 30 36 45 AIR CONDINTIONER LINK CI...

Page 31: ...by broken line KN 27 30 AIR CONDINTIONER LINK CIRCUIT L3 N L2 L1 5 CORE Cable RW 300 500 5X1 5mm2 L 3 N 4 3 CORE Cable 3X1 5mm2 5 6 XT2 2 1 3 5 4 6 INDOOR 3 CORE Cable YZW 300 500 3X1 5mm2 XT1 C1 C B...

Page 32: ...ng only type withoout the link listed by broken line KN 24 27 AIR CONDINTIONER LINK CIRCUIT C 3 CORE Cable 3X2 5mm2 5 XT2 1 2 3 4 6 XT1 C1 N B A INDOOR 5 CORE Cable 5X2 5mm2 Chart 37 18 Power 220 240V...

Page 33: ...ether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood Whether any of the refrigerant is leaked a b c d e f g h i a b c 2 The outdoor unit TEST OPERATI...

Page 34: ...XTRA RESTRICTOR KIT FOR CONNECTION TO THE INDOOR LIQUID VALVE DURING INSTALLATION AS THE ABOVE ILLUSTRATION WARNING WITHOUT THIS KIT THE UNIT WILL NOT OPERATE PROPERLY IN THE HEATING MODE FOR CONNECTI...

Page 35: ...fices on the parkSuite 27 8 Greenhill Road Wayville SA 5034 TEL 08 8372 7866 FAX 08 8372 7816 PERTH Suite 23 350 Cambridge St Wembley WA 6014 TEL 08 9284 0800 FAX 08 9284 0600 NEWCASTLE Suite 3 19 Dar...

Reviews: