INDOOR UNIT INSTALLATION
1. Install the main body
A. The existing ceiling (to be horizontal)
Please cut a quadrangular hole of 880X880mm in the ceiling according to the shape of the installation paper
board.(Refer to Chart3,4)
The center of the hole should be at the same position of that of the air conditioner body.
Determine the lengths and outlets of the connecting pipe, drainpipe and cables.
To balance the ceiling and to avoid vibration, please enforce the ceiling when necessary.
b. Please select the position of installation hooks according to the hook holes in the installation board.
a.
Drill four holes of
M
12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible
hooks (fittings).
Face the concave side of the installation hooks toward the expansible hooks. Determine the length of the
installation hooks from the height of ceiling, then cut off the unnecessary part.
c. Please adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body.
The length could be calculated from Chart5:
Length=H-181+L (in general, L=100mm and is half of the whole length of the installation hook)
If the drainpipe is awry, leakage will be caused by the malfunction of the water-level switch.
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even. The body's
lower part should sink into the ceiling for 10~12mm (Refer to chart 5).
Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well.
Necessary room
$
2500mm
outlet
inlet
outlet
Note: 27 Series A
/
260mm
30/45 Series
A
/
330mm
A
ground
Chart 1
Drain side
Tubing side
A
780 (Hook-location)
840 (Body)
880 (Ceiling hole)
950 (Panel)
(Unit: mm)
780 (Hook-location)
840 (Body)
880 (Ceiling hole)
950 (Panel)
Chart 3
Chart 2
$
1000mm
$
1000mm
$
1000mm
$
1000mm