Page 52
CLS/CLC HT-HPF
402
502
552
602
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power
kW
50.5
60.9
64.7
73.3
Rated current
A
67.9
82.1
83.6
93.5
Max. current (FLA)
A
82.1
99.5
111.1
122.1
Max. start-up current (LRA)
A
258.6
322.3
373.0
384.0
External fuses
(A)
100
125
125
160
Max. cable section (1)
mm
2
35
50
70
70
CLS HT-HPF with pump
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power
kW
52.3
62.7
66.5
75.1
Rated current
A
72.8
87.0
88.5
98.4
Max. current (FLA)
A
87.0
104.4
116.0
147.0
Max. start-up current (LRA)
A
263.5
327.2
378.0
389.0
External fuses
(A)
100
125
125
160
Max. cable section (2)
mm
2
35
50
70
70
Technical data
CLS/CLC HT-HPF
182
202
242
302
352
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power
kW
19.8
26.4
31.0
36.6
44.0
Rated current
A
23.7
32.1
43.4
52.0
60.8
Max. current (FLA)
A
33.6
44.8
51.4
61.4
72.6
Max. start-up current (LRA)
A
117.5
151.1
177.4
207.4
248.0
External fuses
(A)
50
63
63
80
100
Max. cable section (1)
mm
2
16
25
25
35
35
CLS HT-HPF with pump
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power
kW
20.6
27.2
32.5
38.1
45.8
Rated current
A
25.8
34.2
47.2
55.8
65.7
Max. current (FLA)
A
35.7
46.9
55.2
65.2
77.5
Max. start-up current (LRA)
A
119.6
153.2
181.2
211.2
254.0
External fuses
(A)
50
63
63
80
100
Max. cable section (2)
mm
2
16
25
25
35
35
(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
(2) Data which refer to a single pump.
Unit Electrical data
Manuale CLS-CLH1 7.2.2005 10:17 Pagina 52