background image

Roof Top Units

  

HA / 34 /45 /52 /61 / 75 / 89 / 110  RC 

 

Roof Top Unit

11

Any modifications carried out without the approval of Airwell may void the unit warranty.
Mains supply cables must be sized to ensure adequate voltage at the unit terminals when the unit is starting and

during full load operation.
Selection of supply cables must be determined by the following criteria:
1. Length of run supply cables.
2. Maximum starting current of unit – cables must supply adequate voltage at unit terminals for starting.
3. Method of installation of supply cables.
4. Capability of cables to carry unit full load current.
Starting and full load currents are provided on the units circuit diagram.
Short circuit protection must be provided at switchboard using HRC fuses or circuit breakers.
Where the choice of room controls includes either a remote room sensor and/or a set point unit these must be wired

in shielded cable and must not be run in the conduits with the power wiring (240/415 volt) as any induced voltage will

cause unreliable operation of the unit.

PLEASE NOTE

It is essential that the location selection for the thermostat sensor is representative of the space to be controlled and

where it will be readily affected by changes to the general space temperature.
Location adjacent to or in line with supply air outlets, or where its operation may be affected by direct sunlight,

outside doors or other external influences must be avoided.
The wire entry point must also be thoroughly sealed to prevent draughts influencing the operation of the sensor.

Failure to observe the above requirement may result in erratic and unreliable operation of the unit.

REFRIGERANT CHARGE

This heat pump is shipped pre-charged with the correct amount of R22 in the system.  At unit start up, the operating

pressures and temperatures should be checked to verify the unit is properly charged by a qualified refrigeration

mechanic.

WWARNING

s.

    DEFROST CYCLE DRAINAGE

During the heating cycle ice forms on the surface of the outdoor coil. This ice is periodically removed during the unit’s

defrost cycle and fairly large quantities of water (melted ice) will be dumped onto the area beneath the unit. Where

the unit is mounted on a roof this should not be a problem. However, where the free run off of this water is not

acceptable a drain tray of at least 75 mm deep and extending 75mm outside the unit’s dimensions must be installed

beneath the unit and drain piping connected to it.

.

DUCTING REQUIREMENTS

All  duct  designs  and  heat  loads  must  be  calculated  by  a  qualified  air  conditioning  consultant  or  contractor  in

accordance with normal good ducting practices.
Dimensions  of  duct  connections  are  shown  on  the  dimension  sheet.  Connection  to  the  unit  must  be  made  via

flexible connections to prevent transmission of vibration and facilitate easy removal of panel work for major service

access. All ductwork must be insulated against noise and heat transmission.

FRESH AIR INTAKE

If required this must be fitted to the return air ducting as no special provision is made within the unit. All fresh air

intakes must be provided with air filters if they are connected to the ductwork between the return air filter and the

unit.

AIR FILTERS

Air filters are not provided and no provision is made for fitting them within the unit as standard. Air filters should

however be provided by the installing contractor and located in an accessible location between the return air grille

and the unit. These filters must be sized for a maximum face velocity of 2.0 m/sec.

.

ELECTRICAL INSTALLATION

The electrical installation must be carried out by a competent licensed electrician in accordance with local power

supply authority regulations and the appropriate unit wiring diagram.

PLEASE NOTE

INSTALLATION

Summary of Contents for HA 110 RC

Page 1: ...Industrial Range Climatisation Climatisation R 22 HEATPUMP Roof Top Units HA 34 RC HA 45 RC HA 52 RC HA 61 RC HA 75 RC HA 89 RC HA 110 RC INSTALLATION INSTRUCTIONS TH 3886 B 3990132 FROM EMAILAIR...

Page 2: ...king into account specific conditions of the location and the current required for any other appliance connected with the same circuit WARNING Cutoff power supply before starting to work on the applia...

Page 3: ...n transposed HA 34 RC 45RC 52RC HA 61RC HA 75 RC HA 89 RC HA 110 RC MachinERY DIRECTIVE 98 37 CEE Low Voltage Directive DBT 73 23 CEE amended by Directive 93 68 CEE Electromagnetic Compatibility Direc...

Page 4: ...linging the unit care must be taken to prevent rope damage to the paintwork or components In particular the drain connections on the unit must be avoided R 22 END PRODUCT PART NUMBERS COOLING SPECIFIC...

Page 5: ...A A A A m m 1 2 5 2 5 2 6 9 4 G 5 7 5 2 2 3 2 3 1 8 6 G 5 5 8 2 2 3 2 3 1 9 6 G 5 R 22 CONTENTS OF PARCEL R 22 e c n a i l p p a f o e p y T 5 4 A H d j 2 5 A H j d 1 6 A H j d y l p p u s r e w o P...

Page 6: ...ck m m e c n a r a e l c m u m i n i M A B C D E 0 0 6 0 0 8 0 0 6 0 0 4 0 0 0 3 HANDLING INSTALLATION OF THE UNIT Minimum clearance to be provided for maintenance access NET WEIGHT Modell HA 34 HA 45...

Page 7: ...n if possible position the outdoor coil away from the winds to reduce defrost cycle time 6 If possible orient the unit outdoor coil towards the morning sun This increases efficiency in heating and de...

Page 8: ...25 4 O D copper drain 155 390 390 155 85 683 25 duct flanges 156 272 144 535 1120 mounting centres 14 14 234 292 99 561 87 to drain 98 316 107 761 1282 mounting centres 19 19 264 345 100 579 90 to dr...

Page 9: ...85 25 duct flanges 978 1320 1320 155 25 4 O D copper drain 90 to drain 99 806 37 739 130 316 98 264 345 1282 mounting centres 19 19 1320 1320 157 Copper drain 25 4 O D 157 137 508 538 138 68 25 duct...

Page 10: ...on the condensate drain lines Drain port dia 1 CAUTION Never braze the condensate drain pipe to the appliance outlet fittings CAUTION For Heatpump models if the outdoor temperature is likely to fall b...

Page 11: ...essures and temperatures should be checked to verify the unit is properly charged by a qualified refrigeration mechanic WWARNING s DEFROST CYCLE DRAINAGE During the heating cycle ice forms on the surf...

Page 12: ...ts in workmanship or material under normal use and service subject to certain conditions As ECP Australia has not direct control over field work done during installation claims resulting from damage t...

Page 13: ...lication limits of the unit supply air fan see fan curves The associated static pressure must be such that the motor is operating within its normal power rating With all panels in place measure curren...

Page 14: ...ommon filter is either a 25 mm or 50 mm thick permanent type which may be cleaned with the aid of a vacuum cleaner then washed in a weak solution of detergent and warm water However the installer s re...

Page 15: ...ature e Crankcase heater to be energised during off cycle 7 4 Outdoor Coil a Clean fin surfaces as required b Note condition of fans and motors b Clean fillers c Check condition of fan and fan motor M...

Page 16: ...4 5A 25 250 75 25A 21A 96 3A 25 250 89 32A 25 7A 80 75A 32 320 110 32A 28 5A 91A 32 320 ELECTRICAL DIAGRAMS ABBREVIATIONS 2 1 COMPRESSOR SAFETY CIRCUIT KA1 phase inversion detector K1 power contactor...

Page 17: ...t to Elco Motor Colore White HA 34 Fan Medium FM ORANGE Fan Hight FH BROWN TABLE 5 FACTORY WIRING MODEL 34 45 52 61 75 89 110 Adjust of Thermal Relays FT3 Range Adjustement 1 8 2 6A 1 9A 1 2 1 8A 1 5A...

Page 18: ...Roof Top Units HA 34 45 52 61 75 89 110 RC Roof Top Unit 18 WIRING DIAGRAM SE 3038A HA 34 C RC T1PRI T1SEC R1...

Page 19: ...Roof Top Units HA 34 45 52 61 75 89 110 RC Roof Top Unit 19 T1PRI T1SEC R1 WIRING DIAGRAM SE 3039B HA 45 52 61 75 C RC...

Page 20: ...Roof Top Units HA 34 45 52 61 75 89 110 RC Roof Top Unit 20 WIRING DIAGRAM SE 3041B HA 89 110 C RC...

Page 21: ...Roof Top Units HA 34 45 52 61 75 89 110 RC Roof Top Unit 21 T1PRI T1SEC WIRING DIAGRAM 3117A HA 89 110 C RC CONTROL...

Page 22: ...TART UP A SIGNAL FROM THE CONTROLLER WILL CLEAR THIS ALARM Other voltage free contact control types including BMS single stage units with CAC CONTROLLER 24V 24 Volt ACTIVE 1 COMP 2 FAN 3 ELEMENT HEAT...

Page 23: ...CL in the set up routine 2 Shielded cable is recommended for this control The RS485 communication wiring must be twisted pair Control wiring must be kept separate from power wiring 3 An RT or Cont ala...

Page 24: ...CL in the set up routine 3 Shielded cable is recommended for this control The RS485 communication wiring must be twisted pair Control wiring must be kept separate from power wiring 4 An RT or Cont ala...

Page 25: ...AUX CONTACTOR XB 01035 REMOTE SENSOR RS485 TO OTHER UNITS NOTES 1 The remote sensor must be used 2 Unit address is set using DIP switches S9 S12 on the CAC controller 3 Shielded cable is recommended...

Page 26: ...ication wiring must be twisted pair Control wiring must be kept separate from power wiring 4 An RT or Cont alarm may appear in initial start up A signal from BMS will clear this alarm 5 The last contr...

Page 27: ...AX 07 3392 8115 ADELAIDE Offices on the parkSuite 27 8 Greenhill Road Wayville SA 5034 TEL 08 8372 7866 FAX 08 8372 7816 PERTH Suite 15 350 Cambridge St Wembley WA 6014 TEL 08 9284 0800 FAX 08 9284 06...

Reviews: