7
GB-17
Power supply and connecting wires specification
5. WIRING
Separate the low voltage wiring (signal wire) and high voltage wiring (power supply wiring) at least 0.5m
so that they do not pass through the same place together. Proximity may cause electrical interference,
malfunctions, and breakage.
CAUTION
220-240V~ 50Hz
H05VV-F;
3×1.0mm
2
H07RN-F;
5×2.5mm
2
Shielded wire;
2×0.2mm
2
Model
Power Cord(Field Supply)
Indoor/outdoor connecting wiring
(Field Supply)
Indoor
Phase
Frequency and volt
Rated Current
Fuse Rating(Field Supply)
H05VV-F;
3×1.0mm
2
1-Phase
1.0A
10A
Power Cord(Field Supply)
Outdoor
Phase
Frequency and volt
Circuit Breaker(Field Supply)
H07RN-F;
5×2.5mm
2
3-Phase
380-415V 3N~ 50Hz
25A
Shielded wire;
2×0.2mm
2
H05VV-F;
3×1.0mm
2
1-Phase
1.0A
10A
H07RN-F;
5×2.5mm
2
3-Phase
1-Phase
1.0A
10A
3-Phase
32A
45A
Shielded wire;
2×0.2mm
2
FDM036
FDM048
FDM060
NOTE OF FUSE SPECIFICATIONS:
(applicalbe to units adpot R32 refrigerant only, and the fuse is made of ceramic.)
1. The specification of outdoor unit fuse is T20A/250VAC(for <24000Btu/h unit), T30A/250VAC(for
>24000Btu/h unit )
2. The specification of indoor unit fuse is T5A/250VAC, T10A/250VAC.