11-14
CONTROL SYSTEM
SM DEL60Hz 1-E.0 GB
11.12.3
Outdoor Units SW Parameters
Parameter Name
DCR22
DCR25
DCR 35
DCR50
Compressor Parameters
MinFreqC
35
35
35
20
MaxFreqC
52
62
70
77
MinFreqH
38
35
40
26
MaxFreqH
67
73
66
79
Step1Freq
40
43
45
60
Step2Freq
50
55
55
70
Step3Freq
63
63
65
80
Frequency limits as a function of outdoor air temperature
MaxFreqAsOATC
44
50
60
64
MaxFreqAsOAT1H
53
58
60
75
MaxFreqAsOAT2H
45
50
50
60
Compressor Over Heating Protection
CTTOH1
94
94
94
94
CTTOH2
98
98
98
98
CTTOH3
102
102
102
102
CTTOH4
105
105
105
105
CTTOH5
120
120
120
120
Compressor Over Current Protection [A]
CCR01
28
35
40
100
CCR02
30
37
42
105
CCR03
32
39
44
108
CCR04
35
42
47
102
Outdoor Fan Speed (RPM)
OFLOWC
610
600
600
600
OFMEDC
760
OFMAXC
700
760
760
920