12-15
CONTROL SYSTEM
SM GCD030 1-A.0 GB
12.12 Jumper
Settings
12.12.1 Indoor Unit Controller
0 = Open Jumper (disconnect jumper).
1 = Close Jumper (connect jumper).
Self test Jumper – J1
OPERATION
J1
SELF-TEST
1
NORMAL
0
Compensation Jumper – J2
Model
J2 (Default)
Compensation
PNX/PNX18/PNX30/WSA
0
Activated
SX/AC/NSX
1
Deactivated
LS/K/KS/AS/AD/DLS/KN
1
Activated
DLS series are defined by “ model”:
model
Jumper setting
New family definition Model definition
J8
J7
J6
J5
J4
J3
KS+A
0
0
0
1
0
1
DLS
A
LS+A
0
0
0
1
1
0
DLS
B
KS+C
1
0
0
1
0
1
DLS
C
KS+D
1
1
0
1
0
1
DLS
D
Model selection Jumper – J7, J8
Model
J8 J7
A
B
C
D
0 0
0 1
1 0
1 1
J9- Presence Detector /Power Shedding
OPERATION
J9
Presence Detector
0
Power Shedding
1
Jumper – J10
OPERATION
J10
PNX DCI LCD
0
LED
1