![Airwell CKD 30 DCI Service Manual Download Page 11](http://html1.mh-extra.com/html/airwell/ckd-30-dci/ckd-30-dci_service-manual_2880103011.webp)
2-4
PRODUCT DATA SHEET
SM GCD030 1-A.0 GB
2.4
DLS 30 DCI / GCD 030
Model Indoor Unit
DLS 30 DCI
Model Outdoor Unit
GCD 030 R410A
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Capacity
(4)
Btu/hr
25590(5460-30710)
29340(6140-35830)
kW
7.5(1.6-9.0)
8.6(1.8-10.5)
Power input
(4)
kW
2.48(0.55-3.15)
2.68(0.5-2.8)
EER (Cooling) or COP(Heating)
(4)
W/W
3.02 3.21
Energy efficiency class
B
C
Power supply
V
220-240
Ph
1
Hz
50
Rated current
A
11.1
12.0
Power factor
0.97
0.97
Prated (IDU)
W
260
Prated (IDU+ODU)
W
3200
Starting current
A
15
Circuit breaker rating
A
25
INDOOR
Fan type & quantity
Centrifugal x 1
Fan speeds
T/H/M/L
RPM
800/670/550
Air flow
(1)
T/H/M/L
m3/hr
1320/1150/935
External static pressure
Min
Pa
25
Sound power level
(2)
H/M/L
dB(A)
64/61/58
Sound pressure level
(3)
H/M/L
dB(A)
48/44/40
Moisture removal
l/hr
1.5
Condenstate drain tube I.D
mm
22
Dimensions
WxHxD
mm
770x690x260
Net Weight
kg
31
Package dimensions
WxHxD
mm
959x854x315
Packaged weight
kg
33
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type,model
Two Rotary,Sanyo(Sheny) C-7RVN153H0W
Fan type & quantity
Propeller(direct) x 1
Fan speeds
H
RPM
850
Air flow
H
m3/hr
3600
Sound power level
H
dB(A)
66
Sound pressure level
(3)
H dB(A)
56
Dimensions
WxHxD
mm
1040x864x412
Net Weight
kg
66
Package dimensions
WxHxD
mm
1140x930x510
Packaged weight
kg
73.5
Units per pallet
Units
4
Stacking height
units
2 levels
Refrigerant type
R410A
Standard charge
kg(7.5m)
2.5
Additional charge
7.5m<Length
≤
20m:+0g;
20m<Length
≤
30m:+250g;
30m<Length
≤
50m:+1450g;
Connections between
units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.50
Max.height difference
m.
Max.25
Operation control type
Remote control
Heating elements (Option)
kW
Others
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1.4 meter distance from unit.
CONTENTS