If the air conditioner is transferred to a new user, this manual shall be transferred to the user, together
with the conditioner.
Before installation, be sure to read Safety Considerations in this manual for proper installation.
The safety considerations stated below is divided into

Warning

and

Attention

. The matters on

severe accidents caused from wrong installation, which is likely to lead to death or serious injury, are listed
in

Warning

. However, the matters listed in

Attention

are also likely cause the severe accidents.

In general, both of them are the important items related to the security, which should be strictly abided by.
After the installation, perform test run to make sure everything is in normal conditions, and then operate
and maintain the air conditioner in accordance with the User Manual. The User Manual should be delivered
to the user for proper keeping.

Warning

6

Safety Considerations

Please ask the special maintenance station for installation and repair. Water leakage, electric shocks or
fire accidents might be caused from improper installation if you conduct the installation by your own.
The installation should be conducted properly according to this manual. Water leakage, electric shocks or
fire accidents might be caused from improper installation.
Please make sure to install the air conditioner on the place where can bear the weight of the air conditioner.
The air conditioner can

t be installed on the grids such as the non-special metal burglar-proof net. The place

with insufficient support strength might cause the dropdown of the machine, which may lead to personal
injuries.
The installation should be ensured against typhoons and earthquakes, etc. The installation unconformable
to the requirements will lead to accidents due to the turnover of the machine.
Specific cables should be used for reliable connections of the wirings. Please fix the terminal connections
reliably to avoid the outside force applied on the cables from being impressed on the cables. Improper
connections and fixings might lead to such accidents as heating or fire accidents.
Correct shapes of wirings should be kept while the embossed shape is not allowed. The wirings should
be reliably connected to avoid the cover and the plate of the electrical cabinet lipping the wiring. Improper
installation might cause such accidents as heating or fire accidents.
While placing or reinstalling the air conditioner, except the specific refrigerant (R410A), don

t let the air go

into the refrigeration cycle system. The air in the refrigeration cycle system might lead to the cracking or
personal injuries due to abnormal high pressure of the refrigeration cycle system.
During installation, please use the accompanied spare parts or specific parts. If not, water leakage, electric
shocks, fire accidents or refrigerant leakage might be caused.
Don

t drain the water from the drainpipe to the waterspout where may exist harmful gases such as sulfureted

gas to avoid the harmful gases entering into the room.
During installation, if refrigerant leakage occurs, ventilation measures should be taken, for the refrigerant
gas might generate harmful gases upon contacting the flame.
After installation, check if any refrigerant leakage exists. If the refrigerant gas leaks in the room, such things
as air blowing heaters and stoves, etc. may generate harmful gases.
Don

t install the air conditioner at the places where the flammable gases may leak. In case the gas leakage

occurs around the machine, such accidents as fire disasters may be caused.
The drainpipe should be properly mounted according to this manual as to ensure the smooth drainage. In
addition, heat preservation should be taken to avoid condensation. Improper drainpipe mounting might
cause water leakage, which will get the articles at home wet.
The refrigerant gas pipe and liquid pipe should be heat insulated to preserve heat. For inappropriate heat
insulation, the water caused from the condensation will drop to get the article at home wet.

Attention

The air conditioner should be effectively grounded. Electric shocks may occur if the air conditioner is
ungrounded or inappropriately grounded. The wire for earthing shouldn

t be connected to the connections

on the gas pipe, water pipe, lightning rod or telephone.
The breaker for electricity leakage should be mounted. If not, accidents such as electric shocks may happen.
The installed air conditioner should be checked for electricity leakage by being powered.
If the ambient humidity bigger than 80%, when the water discharge hole be blocked or the filter becomes
dirty, or airflow speed change, there maybe leads to condensing water drop down, and at the same time
there maybe some drops of water spit out.

Summary of Contents for AWSI-DCV072-N11

Page 1: ...AWSI DCV072 N11 AWSI DCV096 N11 No 0150513924 Indoor Unit Operation Installation Manual Please read this manual carefully before using Keep this operation manual for future reference...

Page 2: ...refrigerating system should use the unified power switch to ensure that all indoor units are in the state of being powered on at the same time during the operation of air conditioner Your air conditio...

Page 3: ...1 Parts and Functions indoor unit air outlet port air inlet port flue flue Condensated water pan...

Page 4: ...ed for inspection service Air change switch It is used to open and close air change function The mode is as follows No display air change automatic air change RECOVERY air change NORMAL Clock timing a...

Page 5: ...rature setting temperature and unit number Air volume display Display the setting speed Inspection status display Air change display Health function display Unit number display Centralized adress disp...

Page 6: ...th operation function 5 HEALTH Button 21 FILTER Display When the filter need be cleaned you can press the FILTER button for 3s to up down function 20 TIMER Display 19 TIME Display 28 29 30 31 32 33 34...

Page 7: ...ler and the receiver should be max 7m and there should be no obstacle between them Do not throw the remote controller to prevent it from being damaged Battery loading Batteries are fitted as follows R...

Page 8: ...electrical cabinet lipping the wiring Improper installation might cause such accidents as heating or fire accidents While placing or reinstalling the air conditioner except the specific refrigerant R4...

Page 9: ...oximately 2 10 min During defrosting the fan of the indoor unit runs at a low speed or stops while that of the outdoor unit stops running Do not use water heater or like next to the indoor unit and th...

Page 10: ...wind screen 6 Press ON OFF switch off The light on the line controller is off 2 Choose operation mode Press mode switch to change to AUTO FAN ONLY COOL DRY HEAT Remarks Avoid pressing ON OFF switch fr...

Page 11: ...d CLOCK flickers and the time displayed is the real time If not in timing the screen displays the real time If in timing the screen displays the timing time If you want to know the real time go to the...

Page 12: ...d OFF timing are the same the setting is invalid Even in timing condition you may start or close the unit through pressing ON OFF switch Note parts of wired controller explanation 1 The unit starts or...

Page 13: ...re controller is powered off If the wire controller is powered on the above operations will be invalid 2 Function difference between master wire controller and slave one Master wire controller Slave w...

Page 14: ...her than temperature setting unit will run intermittently at LOW speed regardless of FAN setting When room temperature is lower than temperature setting unit will only run FAN operation In HEAT mode w...

Page 15: ...ON OFF button to stop unit 4 Unit stop 3 Adjust fan speed Press FAN button Each press the fan speed changes as follows Air conditioner will run at the selected fan speed When in AUTO mode the unit wil...

Page 16: ...lt in air conditioner s abnormally running If the louver work abnormally stop unit restart and adjust the louver by remote controller In COOL or DRY mode do not leave the louver in downward position f...

Page 17: ...s time adjustment buttons If the button is kept pressed the time will changes quickly It can be adjusted within 24 hours at will Hints After replacing batteries or if a power failure occurs TIMER sett...

Page 18: ...still consume power Air cleaner and shell must be mounted after cleaning Cleaning Air Cleaner Don t rinse the air cleaner with hot water of above to avoid fading and distorting Don t put the air clea...

Page 19: ...e shutdown indoor units refrigerant flows in the short time and make the sounds of refrigerant flowing Otherwise when other indoor units performs heating operation white steam may occur during refrige...

Page 20: ...d the air can t be input from the suspended ceiling where the lengths of the piping between indoor units and outdoor units are within the allowable range refer to Installation of Outdoor Units where t...

Page 21: ...the line control connection line between indoor units and outdoor unit so that they can be connected with indoor units right after installation For the inspection hole the ceiling might be reinforced...

Page 22: ...e equipments the public piping should be lower about 100mm than the wash ports of equipments as shown in the figure Thicker pipes should be used for this application d 1 5m 2m Proper Piping hanging bo...

Page 23: ...well Calculate the design chart and exterior static pressure and select the exhaust pipe with appropriate length and shapes main unit of air conditioner ceiling suface special exhaust port purchased a...

Page 24: ...120 B A unit with filter purchased additionally static pressure box 300m3 h 300m3 h 1200m3 h 1200m3 h simple duct selection Note 1Pa m flux item shape square pipe m3 h m3 min 100 200 300 400 500 600 1...

Page 25: ...uter side of the blast pipe The humidity is high even if the inner side of the suspended ceiling isn t used as a blast pipe in new concrete buildings At this time the whole body should use the thermo...

Page 26: ...re gage to ensure the specified amount or compressor failure can be caused by filling too much or little refrigerant Tubing Materials Specifications 25 4 DCV096 Phosphor deoxybronze seamless pipe TP2...

Page 27: ...indoor and wire controller And be earthed on one side or the unit will not work normally because of interference Note Confirm the terminal connection firmly and do not get in tough with shielded wire...

Page 28: ...ower plug L should be connected to the live wire and plug N connected to null wire while should be connected to the ground wire For the type with auxiliary electrically heating function the live wire...

Page 29: ...A One line control controls multiple units i e 2 16 indoor units as shown in the above figure 1 5 indoor units The indoor unit 5 is the line controlled main unit and others are the ine controlled sub...

Page 30: ...well as the wiring between indoor units Note DCV models are set to remote controlled type before delivery Setting Mode Wireless Remote Controller Socket Dip switch SW01 1 2 3 4 CN21 Socket Null Conne...

Page 31: ...ntrol address the other corresponding address can change automatically meeting as follows Central control address equals to physical address plus 0 or 64 Dip switch setting In the following table 1 is...

Page 32: ...ff correction valve in AUTO mode SW07_1 SW07_2 Tdiff correction valve in AUTO mode 1 SW07_3 26 lock 4 0 0 1 1 Normally without 26 degree lock function defaulted 26 degree lock function is availble In...

Page 33: ...Normal mode TES is unavailable default TES is available 1 0 1 0 1 1 0 0 1 0 1 Run at Mid speed when Hi Speed is selected Quiet running mode Indoor and outdoor 90 meters drop selection Reserved Indoor...

Page 34: ...15 seconds it will automatically quit and keep the last setting Inquiry of fault records of indoor units In the state of startup or shutdown press CHECK button to go into the mode of inquiring faults...

Page 35: ...0V megaohm meter and check if the resistance is above 1M It can t be operated if it is below 1M Connect it to the power supply of outdoor units to energize the heating belt of the compressor To protec...

Page 36: ...ronic waste can be disposed of ate least free of charge to the user b When buying a new product the retailer will take back the old product at least free of charge c The manufacturer will take back th...