HMF Series 24 Version - 0
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
2-
way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position.
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N
·
m.
Be sure to check the gas leakage.
3. Adding the refrigerant if the pipe length >5m
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure the liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
Electronic scale
Summary of Contents for AWAU-YMF009-C12
Page 17: ...HMF Series 17 Version 0 AWSI HMF024 N12 6 2 Outdoor Unit AWAU YMF009 C12 AWAU YMF012 C12...
Page 18: ...HMF Series 18 Version 0 AWAU YMF018 C12 AWAU YMF024 C12...
Page 19: ...HMF Series 19 Version 0...
Page 52: ...HMF Series 52 Version 0 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Page 64: ...HMF Series 64 Version 0 SERVICE MANUAL HMF Series...