![Airwell AWAU-YMF009-C12 Service Manual Download Page 11](http://html1.mh-extra.com/html/airwell/awau-ymf009-c12/awau-ymf009-c12_service-manual_2880013011.webp)
HMF Series 11 Version - 0
Model Indoor Unit
AWSI-HMF024-N12
Model Outdoor Unit
AWAU-YMF024-C12
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Capacity
(1)
Btu/h
21000
EER /COP
(2)
W/W
2.66
Power supply
V/Ph/Hz
220-230V/Single/60Hz
Circuit breaker rating
A
25
INDO
O
R
Fan type & quantity
Cross flow fan x1
Fan speeds
H/M/L
RPM
1220 / 1100 / 900
Air flow
(3)
H/M/L
m3/hr
1100/990/810
External static pressure
Min-Max
Pa
0
Sound pressure level
(5)
H/M/L
dB(A)
49/45/41
Moisture removal
l/hr
2.2
Condensate drain tube I.D
mm
16
Dimensions
WxHxD
mm
1045x235x315
Weight
kg
12
Package dimensions
WxHxD
mm
1135x395x315
Packaged weight
kg
15
O
UTDO
O
R
Refrigerant control
Capillary
Compressor type, model
ROTARY
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
950
Air flow
H/L
m3/hr
2500
Sound pressure level
(5)
H/L
dB(A)
60
Dimensions
WxHxD
mm
820x330x595
Weight
kg
37
Package dimensions
WxHxD
mm
940x415x645
Packaged weight
kg
39.9
Refrigerant type
R410A/830g
Refrigerant charge (standard connecting tubing length)
kg(5m)
1.6
Additional charge per 1 meter
gr / 1m
40
Connections between units
Liquid line
In.(mm)
3/8"(9.52)
Suction line
In.(mm)
5/8"(15.9)
Max.tubing length
m.
25
Max.height difference
m.
10
Operation control type
Remote control
Heating elements
kW
Others
Summary of Contents for AWAU-YMF009-C12
Page 17: ...HMF Series 17 Version 0 AWSI HMF024 N12 6 2 Outdoor Unit AWAU YMF009 C12 AWAU YMF012 C12...
Page 18: ...HMF Series 18 Version 0 AWAU YMF018 C12 AWAU YMF024 C12...
Page 19: ...HMF Series 19 Version 0...
Page 52: ...HMF Series 52 Version 0 ONLY FOR STANDARD BOM CUSTOMIZED FEATURE MAY CHANGE THE PART LIST...
Page 64: ...HMF Series 64 Version 0 SERVICE MANUAL HMF Series...