CONTROL
SYSTEM
11-14
SM HGD-009/012 1-A.1 GB
11.15
Test Mode
11.15.1 Entering Test Mode
Test mode(Mode of testing capacity) can be achieved through special remote control settings as
following table depends on models
Settings of Remote control
Model Mode
(Shown on display)
Cooling Heating
Operation of Remote
control
Display
(2*7 segments)
P0(Minimum capacity)
SPT=16
SPT=27
Show “P0”
P1(Norminal capacity)
SPT=18
SPT=29
Show “P1”
P2(Maximum capacity)
SPT=19
SPT=30
Show “P2”
09/12
P3(Medium capacity)
SPT=17
SPT=28
Press “
light
” button 4
times in 3 secs.
Show “P3”
11.15.2 Unit Operation in Test Mode
Compressor frequency will be set in the following ways.
Model 09
12
Cooling 15Hz
26Hz
P0(Minimum capacity)
Heating 15Hz
26Hz
Cooling 50Hz
62Hz
P1(Norminal capacity)
Heating 59Hz
63Hz
Cooling 88Hz
75Hz
P2(Maximum capacity)
Heating 92Hz
80Hz
Cooling 27Hz
27Hz
P3(Medium capacity)
Heating 30Hz
33Hz
IFAN speed need to set to Turbo before entering test mode.