Service diagnosis
43
Domestic air conditioner
10.3.10 The communication fault between indoor and outdoor
Indoor display
ƵƵƾ
E7
outdoor display LED1 flash 15 times
Method of Communication is detected by checking the indoor PCB and the outdoor PCB.
Malfunction
Detection
Malfunction
Ŷ
The outdoor PCB broken leads to communication fault.
Decision
Ŷ
The indoor PCB broken leads to communication fault.
Conditions
Supposed
Ŷ
Communication wiring disconnected.
Causes
Ŷ
The indoor PCB is broken.
Ŷ
The outdoor PCB is broken.
Ŷ
The Module PCB is broken.
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Summary of Contents for AW-YHDM012-H91
Page 10: ...Pinping diagrams Domestic air conditioner 4ˊPiping diagrams 9 EEV EEV ...
Page 11: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Page 38: ...Service diagnosis 37 Domestic air conditioner ...
Page 57: ...57 Do C omestic air ircuit Diagra conditioner ams r 12 2 Module board circuit diagram ...
Page 59: ...Removal Procedure 1 Removal of Outdoor Panel ...
Page 60: ...Removal Procedure n o i t i d n o C r i A c i t s e m o D 2 ...
Page 61: ...4 Removal Procedure 3 Domestic Air Condition ...
Page 62: ...Removal Procedure 2 Removal of Electrical Box RPHVWLF LU RQGLWLR ...
Page 63: ...Removal Procedure 3 Removal of Fan and Fan Motor RPHVWLF LU RQGLWLR ...
Page 64: ...Removal Procedure 4 Removal of Fan Motor Brcked and Partition ...
Page 65: ...Removal Procedure 7 Domestic Air Condition ...
Page 66: ...Removal Procedure 5 Removal of Compressor and Heat Exchanger ...