Domestic air conditioner
7. Functions and control
7.1 Main functions and control specification
7.1.1 The operation frequency of outdoor unit and its control
7.1.1.1 The operation frequency control of compressor
The operation frequency scope of compressor
˖
Mode
Minimum operation frequency
Maximum operation frequency
Heating
˄
09K/12K
˅
24 Hz /25Hz
65 Hz /85Hz
Refrigeration
˄
09K/12K
˅
24 Hz /25Hz
99 Hz /100Hz
7.1.1.2 The starting of compressor
When the compressor is started for the first time, it must be kept under the conditions of
38Hz,58Hz,88Hz for 30second,one minute, one minute (the overheating protection of the outdoor unit
air-blowing temperature, immediately decrease the frequency when the compressor is overflowing and
releasing the pressure)
ˈ
then it can be operated towards the target frequency. When the machine runs
normally, there’s no such process. After starting the compressor for operation, the compressor should
run according to the calculated frequency, and every determined frequency for protection should be
prior to the calculated frequency.
7.1.1.3 The speeds of increasing or decreasing the frequency of the compressor
The speed of increasing or decreasing the frequency rapidly 1 -----------1HZ/second
The speed of increasing or decreasing the frequency slowly 2 -----------1HZ/10seconds
7.1.1.4 The calculation of the compressor’s frequency
Refrigeration/dehumidification mode:
Pn=(Nh_c-
S_c)*10
ı
50 outdoor environment control
Pn=(Nh_c-
S_c) *10
˘
50 PID control
Heating mode:
Pn=(S_c
-Nh_c)
*10
ı
60 outdoor environment control
Pn=(S_c
-Nh_c)
*10
˘
60 PID control
(Nh_c=indoor
environment temperature S_c=setting temperature)
1
˅
The minimum/maximum frequency limitation
A
ˊ
While refrigerating: F-MAX-r is the maximum operation frequency of the compressor; F-MIN-r is the
minimum operation frequency of the compressor.
B
ˊ
While heating: F-MAX-d is the maximum operation frequency of the compressor; F-MIN-d is the
minimum operation frequency of the compressor.
2
˅
The frequency limitation which is affected by the environment temperature.
(Wh_c= environment temperature)
Heating mode:
Serial No.
Temperature scope
Frequency limitation
˄
09K/12K
˅
1
Wh_c<-12
Max_hz1 99HZ/99 HZ
2
Wh_c<-8
Max_hz2 99HZ/99 HZ
Summary of Contents for AW-YHDM012-H91
Page 10: ...Pinping diagrams Domestic air conditioner 4ˊPiping diagrams 9 EEV EEV ...
Page 11: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Page 38: ...Service diagnosis 37 Domestic air conditioner ...
Page 57: ...57 Do C omestic air ircuit Diagra conditioner ams r 12 2 Module board circuit diagram ...
Page 59: ...Removal Procedure 1 Removal of Outdoor Panel ...
Page 60: ...Removal Procedure n o i t i d n o C r i A c i t s e m o D 2 ...
Page 61: ...4 Removal Procedure 3 Domestic Air Condition ...
Page 62: ...Removal Procedure 2 Removal of Electrical Box RPHVWLF LU RQGLWLR ...
Page 63: ...Removal Procedure 3 Removal of Fan and Fan Motor RPHVWLF LU RQGLWLR ...
Page 64: ...Removal Procedure 4 Removal of Fan Motor Brcked and Partition ...
Page 65: ...Removal Procedure 7 Domestic Air Condition ...
Page 66: ...Removal Procedure 5 Removal of Compressor and Heat Exchanger ...