D.P.S.
LOCK
3
2
1
2
3
1
COM
N/O
N/C
(WHT/RED)
(PUR)
(YEL)
(W
HT
)
(B
LK
)
(R
ED
)
(PUR)
1
N/O
N/C
COM
KEY SWITCH
LOCK STATUS
N/C
N/O
COM
SWITCH
(BLU)
(WHT)
(RED)
(RED)
(PUR)
(BLK
)
(BLK
)
(YEL
)
DOOR POSITION SWITCH N/C (PIN 3)
UNLOCK SIGNAL 120VAC, 1 SEC (PIN 1)
120 VAC NEUTRAL (PIN 3)
LOCK STATUS SWITCH COMMON (PIN 6)
VOID
DOOR POSITION SWITCH COMMON (PIN 1)
DOOR POSITION SWITCH N/O (PIN 2)
(RED)
LOCK STATUS SWITCH N/O (PIN 2)
LOCK STATUS SWITCH N/C (PIN 5)
MOLEX #03-09-1064
Pins: (5X) FEMALE .093 DIA
FIELD SIDE WIRING
PIGTAIL
MOLEX #03-09-2062
Pins: (5X) MALE .093 DIA
MOLEX #03-06-1032
Pins: (3X) FEMALE .062 DIA 24-18 AWG
TINNED AMP#350628-1
MOLEX #03-06-2032
Pins: (3X) MALE .062 DIA 24-18 AWG
TINNED AMP #350629-1
(NOT REQUIRED WHEN USING
D.P.S. OF OTHER MANUFACTURER)
2
5
6
3
(OPTION)
MOLEX
#19-09-2029
Pins: (2X) MALE
.093 DIA
120VAC
SOLENOID
(CONT DUTY)
1
2
5
6
3
(RED)
(YEL)
( )
( )
KEY SWITCH N/O
KEY SWITCH COMMON
MOLEX #19-09-1029
Pins: (2X) FEMALE .093 DIA
B
CHK
DRAWN
DESCRIPTION
ECN
REV
REVISIONS
EL-9912S
NONE
4/9/14
RLP
WIRING DIAGRAM
9912S 120VAC
SOLENOID LOCK
A
NOTES:
1. SOLENOID LOAD: 120VAC 10A INRUSH, .6A SEATED
2. SWITCH CONTACTS: 5A.
3. SCHEMATIC SHOWN WITH DOOR IN THE CLOSED AND LOCKED
(SECURE) POSITION.
4. PLUGS AND RECEPTACLES INSIDE LOCK NOT SHOWN.
5. FOR SERIES LOCK STATUS AND DOOR POSITION SWITCH OPERATION,
CONNECT LOCK FIELD SIDE WIRING YELLOW WIRE (LOCK STATUS SWITCH
N/O)AND DPS FIELD SIDE PURPLE WIRE (DPS SWITCH N/O). CHECK
CONTINUITY BETWEEN LOCK FIELD SIDE PURPLE (LOCK STATUS SWITCH
COM) AND DPS FIELD SIDE WHT/RED (DPS SWITCH COM).
6. ALWAYS INSTALL IN ACCORDANCE WITH LOCAL REGULATIONS AND
THE NATIONAL ELECTRIC CODE (NEC).
7. GROUND LOCK CASE IN ACCORDANCE WITH ARTICLE 250 OF THE
NATIONAL ELECTRICAL CODE