background image

 

 

 

 

 

 

 

CLEVER CONTROL 

Version: V3 

 

INSTALLATION AND FUNCTIONING MANUAL 

USER AND BASIC VERSION

                                                                                        

 

 

Please, read these instructions carefully before attempting installation 

 

 

SECURITY ADVISE SIMBOLS 

 

 

Attention, Danger, Safety Advice! 

                

    

Danger from electric current of high voltage! 

                

                         

Injuries risk! 

                  

  

                   

  

Important Information!

 

 

 

 

 

 

 

 

 

AIRDOM07100-R2 (03-02-16) 

Summary of Contents for CLEVER CONTROL V3

Page 1: ...UAL USER AND BASIC VERSION Please read these instructions carefully before attempting installation SECURITY ADVISE SIMBOLS Attention Danger Safety Advice Danger from electric current of high voltage I...

Page 2: ...S 21 User Menu Basic Configuration WORKING PROGRAM FAN HEATERS 22 User Menu Basic Configuration CONFIGURATION INITIAL 23 User Menu Basic Configuration Configuration NAME 24 User Menu Basic Configurati...

Page 3: ...ver Control has 3 grades of comfort and energy efficiency which can be adjusted in all manual and automatic programs Eco mode uses the less energy possible without compromising too much the comfort wh...

Page 4: ...ation mode user can set the minimum maximum of many parameters like ventilation speed or heating when door is open closed set the temperatures for day night and air outlet the door delay etc Advanced...

Page 5: ...tion INTELLIGENT PCB If more than one PCB connected in serial using Modbus protocol you should turn ON the 3 switches inside the Clever Control and use 3 jumpers at CN3 CN6 and CN7 according to the wi...

Page 6: ...6 CONNECTION DIAGRAM TEMPERATURE SENSOR SHIELDED CABLE CONNECTION DIAGRAM AIR CURTAIN 1 Clever Control managing 1 unit 1 PCB...

Page 7: ...RAM AIR CURTAIN 1 Clever Control managing multiple units 1 PCB Please consult the operating manual of the air curtain for multiple units connection Connection Diagram FAN HEATER 1 Clever Control manag...

Page 8: ...N HEATER 1 Clever Control managing multiple units 1 PCB Connection Diagram HORIZONTAL FAN HEATER 1 Clever Control managing multiple units 1 PCB Please consult the instruction manual of the fan heater...

Page 9: ...9 Wiring Diagram 1 Clever Control with 1 Intelligent PCB...

Page 10: ...10 Wiring Diagram 1 Clever Control with 2 Intelligent PCB...

Page 11: ...00000001 10000000 2 00000010 01000000 3 00000011 11000000 4 00000100 00100000 5 00000101 10100000 6 00000110 01100000 7 00000111 11100000 8 00001000 00010000 9 00001001 10010000 10 00001010 01010000 3...

Page 12: ...R TFT CONTROL MAIN STATE SCREEN Main state screen indicates of the most important settings including Ventilation speed heating temperatures door state working mode and program filter state day hour ti...

Page 13: ...evice externally or by the BMS UNIT LOCKED Indicates that the unit is locked Unit does not work until you unlock it by code CONTROL LOCKED Indicates that the control is locked Unit works but user need...

Page 14: ...then arrows buttons will modify the heating If you press again then arrows modify the temperature set Auto Modifies only the Set temperature Menus Scroll through option left or editing value between a...

Page 15: ...can edit an option USER MENU SCREEN 1 Select Operation Mode Automatic or Manual Functioning Select Energy Saving Mode Eco Uses the less energy possible Medium In between Eco Comfort modes Comfort Spe...

Page 16: ...as Disable To activate to turn it into Enable and press button to activate it and show all the options TIME PROGRAMMER MENU SCREENS 1 y 2 Enable Disable Time Programmer Select Day Type group Create fr...

Page 17: ...e programmed daily with desired schedule Mon Fri Monday to Friday Mon Sat Monday to Saturday Mon Sun Monday to Sunday Mon Fri Sat Monday to Friday and separately Saturday Mon Fri Sat Sun Monday to Fri...

Page 18: ...n Confirm Should press to confirm your selection and go back to Timer general menu Delete If you want to delete the editing action select Yes and press User Menu ADJUST TIME This function adjusts the...

Page 19: ...and go back to general User Menu User Menu BASIC CONFIGURATION MENU In Basic Configuration mode the technician can configure the main parameters of the clever control BASIC CONFIGURATION SCREEN MENU...

Page 20: ...eating unheated electrical heated water heated heat pump Energy saving mode Eco Medium or Comfort Manual P1 Manually you can select ventilation speed and heating stage also with heat pump units you ca...

Page 21: ...nergy saving mode P2 Functioning according to o Set and external temperature o Door state o Energy saving mode P3 4 Functioning according to o Door opened Set Temperature and External Temperature o Do...

Page 22: ...omfort nothing is modified Medium heating is stopped Eco stops the air curtain Automatic Depending on program Clever will regulate itself the ventilation and heating thanks to its temperature sensors...

Page 23: ...default Unit Modbus address Select the fan speed Air Curtains 2 or 5 Select the heating Air unheated Electrical heated Water heated or Heat Pump New questions options can appear if required CONFIGURA...

Page 24: ...T Enter name less than 12 digits 1 Use Scroll Up Down buttons to move through all characters available Press button to select and move to next character 2 If the name is completed before reaching the...

Page 25: ...s that will activate the General Alarm If only 1 of those alarms is activated the general alarm will be also activated GENERAL ALARM MENU SCREEN 1 Overheating Alarm Autocooling Alarm Dity Filter Alarm...

Page 26: ...eating alarm It indicates that there is an overheating inside the fans of the unit Heating Lock Alarm It indicates that the heating has been blocked Air Flow alarm It indicates that the airflow is too...

Page 27: ...p Down User Menu Basic Configuration Parameters SPEED buttons to move and select an option When option is highlighted in blue press button to enter and edit Min Max Speed when Door Open Min Max Speed...

Page 28: ...he heat pump when door closes waiting the selected minutes If door is opened again before this time elapses heat pump will not be turned OFF User Menu Basic Configuration Parameters HEATING Min Voltag...

Page 29: ...et User Menu Basic Configuration Parameters Temperature CALIBRATION Sensors Calibration These parameters allow to calibrate each temperature sensor with X C plus or minus degrees User Menu Basic Confi...

Page 30: ...t nominal speed or heating when you open the door you can program at temporized door out signal how many seconds the door should remain closed while the air curtain is preparing itself Once this time...

Page 31: ...tects how many times the door is open for the last minutes and adapts the door delay times and strengths to those conditions in order to save energy Fixed You can set how many seconds will stay at ste...

Page 32: ...Menu Basic Configuration COUNTERS Filter Hours To Next Revision It displays the hours without changing the filter total hours before filter alarm 50 300 working 50h since last filter alarm and remain...

Page 33: ...ly for professionals please consult If you want to protect the control from end users you can lock the control or the unit User protections Control Locked Code 1234 by default unit will remain working...

Page 34: ...Advanced Configuration ADVANCED PARAMETERS Intervals Intervals are used at automatic programs to modify the ventilation and heating in order to have the most efficient separation Set Ambient Temp 2 C...

Page 35: ...puts Modify the functions of Analog Outputs Temperature sensors Modify the functions of temperature sensors Communications Configure the communications You can select a function to each Digital IN Eac...

Page 36: ...lt Sensor 1 Outdoor Sensor 2 Air Discharge Sensor 3 Inside Controller Enabled Yes Inside sensor has priority to the controller s one If it s not connected automatically uses the TFT control When you c...

Page 37: ...37 Connections and Functions IN OUT of Digital Analogic and Temperature sensors...

Page 38: ...38...

Page 39: ...39 There is an ADVANCED MANUAL that explains deeply the functioning and configuration of all functions of Digital IN Digital OUT Analog IN Analog OUT...

Page 40: ...inning of this manual you can see the default functions of each entrance There are more functions than entrances so you can select the most appropriate to cover your needs advanced menu All digital IN...

Page 41: ...lever only 1 manager You can lock using the same code of TFT or another different then people won t be able to unlock from TFT as they won t know the code 2 Stop the timer to avoid undesired ON Day Ni...

Page 42: ...2 At the following page there are all the needed Modbus orders to manage the units All changes will not be saved if the power supply stops To avoid it after any order you have to save the configuratio...

Page 43: ...in 2 halves Identify wall connection In case of not having a wall switch box use Clever s wall support accessory Mount the back cover inside the wall switch Connect RJ11 Cable to Clever s PCB connect...

Reviews: