En-6
7. TURNING ON THE POWER
CAUTION
Check that the power supply voltage is within the
•
speci
fi
ed range. If a power supply voltage outside the
speci
fi
cation is input, it will cause trouble.
Recheck the wiring. Incorrect wiring will cause trouble.
•
(1) Check the Network Convertor wiring.
(2) Check the wiring and switch settings for the VRF system
and turn on the power for the VRF system. For the wiring
and switch setting method, refer to the installation manual
of each unit.
(3) Set the Jumper switch 1 (JP1) in order to set “Back up
battery ON”. (Fig.)
(This is necessary in order to save the initial setting data
and commissioning data to SRAM.)
BATTERY_ON
BATTERY_ON
BATTERY ON
BATTERY OFF
Fig.
(4) Turn on the power for the Network Convertor.
Note: In procedure (3), the purpose of setting Jumper switch
(JP1) is to make the backup battery effective. The
backup battery can save the Tool for Network Convertor
and Network Integration Tool setting information.
Therefore, it is not necessary to keep effective before
those setting works are done.
The Network Convertor is initialized for a period of
•
approximately a few seconds after the power is turned on.
is displayed on D19 during this period.
After initial setting completely, the operation mode will be
•
started.
Anyone of the following indication will displayed:
•
: VRF Network address allocation is not regis-
tered by using Tool for Network Convertor
: Binding and Commissioning is not executed
: Normal Mode (Ready for operation)
: Others (Refer to “11. LED DISPLAY (D19)”
for more detail.)
D14
D14
* Network Convertor does not operate during initialization.
* If an error occurs, the D9 or D14 LED lights or
fl
ashes, or
the error code is displayed on the right side of the D19 LED
display.
8. ADDRESS SETTING
Setting up more than 1 Network Convertor in 1 VRF
•
network system is prohibited.
When setting address, please be sure that the address
•
of Network Convertor is not overlap the address of
other controller like, Touch Panel Controller & Network
Convertor for Group Remote Controller.
SWITCH POSITION
SW3 SW4
JP1*
SW7
SW2
SW1
D19
1.
Turn on the power of Network Convertor.
2.
3.
Press SW3 (mode button) to set special mode “2”.
Special mode “2” is the address setting mode.
4.
Press SW4 (set button). Present address is displayed.
Following steps are necessary for setting address of Network
Convertor.
Ex.) Address No.15
5.
Press SW3 (mode button) to select the address.
The displayed address changes as follows each time
the mode button is pressed.
6.
Press SW4 (set button) to set the selected address.
A01
A02
A00
A15
Ex.) Address No.3
is selected.
Ex.) Address No.3 is set.
This is “Service Pin”.
Neuron ID is sent upon pushing
BMS service switch (SW2)
Select the special mode by pressing and releasing
SW7 (reset button) while holding down SW4 (set
button) until special mode “1” (Blinking) is displayed.
Please keep holding down SW4 (set button) a few
seconds after releasing the SW7 (reset button).
When SW3 (mode button) is pressed, special mode
changes from ‘1’ to ‘4’ (Blinking) as the as shown in the
above mentioned way.