En-5
CAUTION
Before opening the case of this unit, completely discharge
•
static electricity charged on your body. Otherwise, parts
break-down could result.
Do not touch the circuit board and circuit board parts
•
directly with your hands.
Otherwise, injury or electric shock could result.
Tightening the mounting screws too tight will damage the
•
case of this unit.
Be careful so that the cover does not fall after the cover
•
screws are removed.
Otherwise, injury could result.
6.1. Connecting the power supply cable
(1) Use the 4 screws (M4 × 4 mm) provided to mount the
Network Convertor to the behind ceiling, wall,
fl
oor or other
suitable location.
(2) Remove the 4 screws (M4 × 4 mm), and then remove the
cover.
(3) In order to pass the power supply cable through the
Network Convertor, please open a hole on the grommet
(small) with a knife etc..
Please be careful not to hurt hands or damage the
•
equipment.
Please make the hole suitable for the wiring diameter.
•
Please pay attention that there is a possibility of insects
invade when the hole is too large.
(4) Please lead in the power supply cable in the Network
Convertor through the grommet (small).
(5) Please connect the power supply cable with each terminal
block. Please connect the earth.
Please tighten the screw by the tightening torque in the
•
following table.
(6) Please
fi
rmly tighten the power supply cable and the
binder clamp on the binder (accessory).
POWER
SUPPLY
L
N
⬉⑤
Ground
Binder
Power supply cable
Connecting the power supply cable
Binder
Cable
Binder clamp
POWER
SUPPLY
L
N
⬉⑤
Grommet
(Small)
Cut
0.8 to 1.2 N • m (8 to 12 kgf • cm)
Tightening torque for installing cables to terminal block
6.2. Connecting the transmission cables
(1) Turn the power off.
(2) In order to pass the transmission cable through the
Network Convertor, please open a hole on the grommet
(large) with a knife etc
Please be careful not to hurt hands or damage the
•
equipment.
Please make the hole suitable for the wiring diameter.
•
Please pay attention that there is a possibility of insects
invade when the hole is too large.
(3) Please lead in the transmission cable in the Network
Convertor through the grommet (large).
(4) Please connect the transmission cable with each terminal
block.
Please tighten the screw by the tightening torque in the
•
following table.
(5) Please
fi
rmly tighten the transmission cable and the binder
clamp on the binder (accessory).
(6) Check if the wirings are connected together completely.
(7) Once the wiring of the cables has been completed, mount
the cover to the Network Convertor. Use the screws
(M4 × 4 mm) to mount the cover.
(8) The procedure for shutting the cover of Network Convertor
should be performed after all setting works are complete.
When continue with setting works, please do not close the cover.
X1
X2
B1
B2
TRANSMISSION
NO HIGH VOLTAGE
VRF
LON
⽕ℶ
ֵো㒓
Binder
Connecting the transmission cables
Transmission cable to
L
ON
W
ORKS®
Network
Transmission cable
to VRF Network
Grommet (Large)
Binder
Cable
Binder clamp
X1
X2
B1
B2
TRANSMISSION
NO HIGH VOLTAGE
VRF
LON
⽕ℶ
ֵো㒓
Cut
Cut
0.8 to 1.2 N • m (8 to 12 kgf • cm)
Tightening torque for installing cables to terminal block