AirStage UTY-VLGX Installation Manual Download Page 5

En-5

 

CAUTION

Before opening the case of this unit, completely discharge 

• 

static electricity charged on your body. Otherwise, parts 
break-down could result.

Do not touch the circuit board and circuit board parts 

• 

directly with your hands.
Otherwise, injury or electric shock could result.

Tightening the mounting screws too tight will damage the 

• 

case of this unit.

Be careful so that the cover does not fall after the cover 

• 

screws are removed. 
Otherwise, injury could result.

6.1. Connecting the power supply cable

(1)  Use the 4 screws (M4 × 4 mm) provided to mount the 

Network Convertor to the behind ceiling, wall, 

fl

 oor or other 

suitable location.

(2)  Remove the 4 screws (M4 × 4 mm), and then remove the 

cover.

(3)  In order to pass the power supply cable through the 

Network Convertor, please open a hole on the grommet 
(small) with a knife etc..

Please be careful not to hurt hands or damage the 

• 

equipment. 
Please make the hole suitable for the wiring diameter.

• 

Please pay attention that there is a possibility of insects 
invade when the hole is too large.

(4)  Please lead in the power supply cable in the Network 

Convertor through the grommet (small). 

(5)  Please connect the power supply cable with each terminal 

block. Please connect the earth.

Please tighten the screw by the tightening torque in the 

• 

following table. 

(6)  Please 

fi

 rmly tighten the power supply cable and the 

binder clamp on the binder (accessory).

POWER
SUPPLY

L

N

⬉⑤

Ground

Binder

Power supply cable

Connecting the power supply cable

Binder

Cable

Binder clamp

POWER

SUPPLY

L

N

⬉⑤

Grommet 
(Small)

Cut

0.8 to 1.2 N • m (8 to 12 kgf • cm)

Tightening torque for installing cables to terminal block

6.2. Connecting the transmission cables

(1)  Turn the power off.
(2)  In order to pass the transmission cable through the 

Network Convertor, please open a hole on the grommet 
(large) with a knife etc

Please be careful not to hurt hands or damage the 

• 

equipment. 
Please make the hole suitable for the wiring diameter.

• 

Please pay attention that there is a possibility of insects 
invade when the hole is too large.

(3)  Please lead in the transmission cable in the Network 

Convertor through the grommet (large).

(4)  Please connect the transmission cable with each terminal 

block.

Please tighten the screw by the tightening torque in the 

• 

following table. 

(5)  Please 

fi

 rmly tighten the transmission cable and the binder 

clamp on the binder (accessory).

(6) Check if the wirings are connected together completely.
(7)  Once the wiring of the cables has been completed, mount 

the cover to the Network Convertor. Use the screws 
(M4 × 4 mm) to mount the cover.

(8)  The procedure for shutting the cover of Network Convertor 

should be performed after all setting works are complete.

When continue with setting works, please do not close the cover.

X1

X2

B1

B2

TRANSMISSION

NO HIGH VOLTAGE

VRF

LON

⽕ℶ

ֵো㒓

Binder

Connecting the transmission cables

Transmission cable to
L

ON

W

ORKS®

 Network

Transmission cable
to VRF Network

Grommet (Large)

Binder

Cable

Binder clamp

X1

X2

B1

B2

TRANSMISSION

NO HIGH VOLTAGE

VRF

LON

⽕ℶ

ֵো㒓

Cut

Cut

0.8 to 1.2 N • m (8 to 12 kgf • cm)

Tightening torque for installing cables to terminal block

9708436012-02_IM_EN.indd   5

9708436012-02_IM_EN.indd   5

2011-1-20   17:43:49

2011-1-20   17:43:49

Summary of Contents for UTY-VLGX

Page 1: ...mensions 3 5 WIRING 3 5 1 Wiring method 4 6 INSTALLING THE NETWORK CONVERTOR 4 6 1 Connecting the power supply cable 5 6 2 Connecting the transmission cables 5 7 TURNING ON THE POWER 6 8 ADDRESS SETTING 6 9 INITIAL SETTING SOFTWARE 7 10 BINDING COMMISSIONING NOTICE 7 11 LED DISPLAY D19 7 INSTALLATION MANUAL For authorized service personnel only PART NO 9708436012 02 ...

Page 2: ...ause the control system to malfunction preventing the unit from operating normally Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Do not use the unit for special purposes such as storing food raising animals growing plants or preser...

Page 3: ...ctric shock Install the indoor and outdoor units power supply cable transmission cable and remote control cable 1 m away from television and radio to avoid distorted images and noise Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermeasures Otherwise it will cause trouble or electric shock or fire Confirm the n...

Page 4: ... shock fire etc Install at a place that can withstand the weight of the unit and install positively so that the unit will not topple or fall When installing this unit make sure that there are no children nearby Otherwise injury or electric shock could result Install a circuit breaker Otherwise electric shock or fire could result 5 1 Wiring method VRF Outdoor unit Indoor unit Transmission cable non...

Page 5: ...ing the power supply cable Binder Cable Binder clamp POWER SUPPLY L N Grommet Small Cut 0 8 to 1 2 N m 8 to 12 kgf cm Tightening torque for installing cables to terminal block 6 2 Connecting the transmission cables 1 Turn the power off 2 In order to pass the transmission cable through the Network Convertor please open a hole on the grommet large with a knife etc Please be careful not to hurt hands...

Page 6: ...ommissioning is not executed Normal Mode Ready for operation Others Refer to 11 LED DISPLAY D19 for more detail D14 D14 Network Convertor does not operate during initialization If an error occurs the D9 or D14 LED lights or flashes or the error code is displayed on the right side of the D19 LED display 8 ADDRESS SETTING Setting up more than 1 Network Convertor in 1 VRF network system is prohibited...

Page 7: ...Block in the Network Convertor and the Network Convertor if register the changed XIF file in according to the Tool for Network Convertor Important Network Convertor will not operate if VRF network system address Indoor Outdoor units address allocation information are not registered to Network Convertor XIF data information and VRF network system address allocation information must not be same Bind...

Reviews: