En-8
For “Operation” and “Input method” switching, perform the settings by
“External Input Setting” of menu operation.
For details of setting method, refer to the operating manual.
“Operation”
“Emergency Stop”
“All On/All Off” (Bach start/stop)
“Input Method”
“Edge”
“Pulse”
External output function
6. 6. 4
CN9
PCB
1
3
4
+
+
+
+
-
-
-
-
*3)
2
DC power
supply 12V
connected unit
Connected
load *2
Connected
load *2
Provide a DC12V power supply. Select a power supply capacity
*1.
with an ample surplus for the connected load.
Do not impress a voltage exceeding 12V across pins 1-2, and
3-4
The allowable current is DC15mA or less. Provide a load resis-
*2.
tance such that the current becomes DC15mA or less.
Polarity is [+] for pins 1,3 and [-] for pins 2,4.
*3.
Terminal
CH
pin
Condition
CN9
CH1
4
12V: 1 or more registered indoor units are
operating.
3
0V:
All registered indoor units are
stopped.
CH2
2
12V: (1) An error occurs at 1 or more
registered indoor unit.
(2)
An error occurs at remote control-
ler.
1
0V: (1) All registered indoor units are
operating normally.
(2)
Remote controller is operating
normally.
Wiring method
6. 6. 5
When using the external input/output function, the connection cable
is drawn out as shown in the
fi
gure below.
Fix the connection cable securely using the cable tie.
Ex. 1: When the cable is drawn out from the top of this unit:
Cutting out
Connection cable
Cable tie
Ex .2: When the cable is drawn out from the back of this unit:
TURNING ON THE POWER
7.
CAUTION
Check that the power supply voltage is within the speci
fi
ed
▪
range. If a power supply voltage outside the speci
fi
cation is
input, it will cause trouble.
Recheck the wiring. Incorrect wiring will cause trouble.
▪
After installation work is completed, check the following contents:
Is Central remote controller power supply cable and transmission
cable wiring work complete?
Does the power supply match the rating of the Central remote
controller?
Turn on the power of Central remote controller. Since there is no
power switch at this controller main unit, turn on the power by
means of the power distribution panel (breaker).
If the following installer setting screen is displayed at the screen
of the Central remote controller panel, installation work is com-
plete.
For setting and operating of the Central remote controller, refer to the
separate operating manual.
Since there is some kind of a problem when the installer setting
*
screen does not appear, recheck the work contents.