AirStage AUXK018GLEH Installation Manual Download Page 7

En-6

6.  ELECTRICAL WIRING

 

WARNING

Electrical work must be performed in accordance with this Manual by a person certified 
under the national or regional regulations. Be sure to use a dedicated circuit for the unit. 
An insufficient power supply circuit or improperly performed electrical work can cause 
serious accidents such as electric shock or fire.

Before starting work, check that power is not being supplied to the all units.

For wiring, use the prescribed type of cables, connect them securely, making sure that 
there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as overheat-
ing the terminals, electric shock, or fire.

Securely install the electrical box cover on the unit. 
An improperly installed electrical box cover can cause serious accidents such as electric 
shock or fire through exposure to dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 
could result.

Use the included connection cables and power cables or ones specified by the manu-
facturer. Improper connections, insufficient insulation, or exceeding the allowable current 
can cause electric shock or fire.

Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insufficient insulation, or exceeding the allowable current can 
cause electric shock or fire.

Match the terminal block numbers and connection cable colors with those of the outdoor 
unit (or RB unit). Erroneous wiring may cause burning of the electric parts.

Securely connect the connection cables to the terminal board. In addition, secure the 
cables with wiring holders. Improper connections, either in the wiring or at the ends of 
the wiring, can cause a malfunction, electric shock, or fire.

Always fasten the outside covering of the connection cable with the cable clamp. (If the 
insulator is chafed, electric discharge may occur.)

Install an earth leakage breaker. In addition, install the earth leakage breaker so that the 
entire AC main power supply is cut off at the same time. Otherwise, electric shock or fire 
could result.

Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cables so as not to be direct touched with your hand.

Perform wiring work in accordance with standards so that the air conditioner can be 
operated safely and positively.

Connect the connection cable firmly to the terminal board. Imperfect installation may 
cause a fire.

If the supply cable is damaged, it must be replaced by the manufacturer, its service 
agent or similarly qualified persons in order to avoid a hazard.

 

CAUTION

Earth (Ground) the unit. 
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 
telephone earth (ground) cable. 
Improper earthing (grounding) may cause electric shock.

Do not connect power supply cables to the transmission or remote controller terminals, 
as this will damage the product.

Never bundle the power supply cable and transmission cable, remote control cable 
together. Separate these cable by 50 mm or more. Bundling these cables together will 
cause miss operation or breakdown.

When handling PCB, static electricity charged in the body may cause malfunction of the 
PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor units for more than 10 seconds to discharge static 

electricity charged in the body.

• Do not touch terminals of parts and patterns implemented on PCB.

6.1.  Electrical requirement

• Select the power cable type and size 

in accordance with relevant local and 
national regulations.

• Specifications for local wiring power cord 

and branch wiring are in compliance with 
local code

Voltage rating

230 V

Operating 

range

198 to 264 V (50 Hz)
198 to 253 V (60 Hz)

• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Breaker should be installed at every refrigerant system. Do not use a breaker in a different 
refrigerant system.
Refer to the table for the breaker specifications of each installation condition. Perform 
the power crossover wiring within the range of the same refrigerant system. When the 
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 
below.

A. Current breaker requirements

Model

MCA

MFA

• MCA: Minimum Circuit Ampacity
• MFA: Maximum Fuse Ampacity

When the power crossover wiring is done, 
make it so that the total of the MCA of the 
connected RB units and indoor units does not 
exceed the 15 A. For RB unit  MCA, refer to 
the RB unit  installation manual.
If the capacity of connected RB units and 
indoor units exceeds the upper limit, either 
add breakers or use a breaker with a greater 
capacity.

AUXM018GLEH

0.24 A

20 A

AUXM024GLEH

0.29 A

AUXM030GLEH

0.50 A

AUXK018GLEH

0.41 A

AUXK024GLEH

0.41 A

AUXK030GLEH

0.46 A

AUXK034GLEH

0.46 A

AUXK036GLEH

0.57 A

AUXK045GLEH

0.81 A

AUXK054GLEH

1.04 A

B. Earth leakage breaker requirements

Breaker capacity

Maximum connect-
able “indoor units” 

or “indoor units + 

RB units” (*1)

*1:  Heat pump type: indoor units, 

Heat recovery type: indoor units 
and RB units.

*2:  If the 100 mA capacity breaker is 

not provided, split the quantity of 
the indoor units into small groups 
of 9 units or less and provide a 
breaker with capacity of 30 mA for 
each group.

30 mA, 0.1 sec or less

44 or less

100 mA, 0.1 sec or less

45 to 148 (*2)

6.1.1. Cable specifications

Recommended 

cable size (mm²)

Cable type

Remark

Power supply cable

2.5

Type245 IEC57 
or equivalent

2 Cable + earth (ground)

Transmission cable

0.33

LONWORKS® 
compatible cable

22 AWG LEVEL 4 (NEMA) 
non-polar 2 core, twisted pair 
solid core diameter 0.65 mm

Remote controller 
cable (2-wire type)

0.33 to 1.25

Sheathed PVC 
cable *1

Non-polar 2 core, twisted 
pair

*1:  Use shielded cable in accordance with local rules for remote controller cables.

6.2.  Wiring method

*2

*2

*2

*3

*3

*3

Outdoor unit or RB unit *1

Transmission

Transmission

Indoor unit

Remote controller 

(Master)

Power supply

Indoor unit

Indoor unit

Power supply

Remote 
 control

Breaker

Breaker

Breaker

Remote controller 

(Slave)

Remote controller

*1:  When connecting to the Heat Recovery System, refer to the installation manual of the 

RB unit.

*2:  Earth (Ground) the remote controller if it has an earth (ground) cable.
*3:  The 3-wire type remote controller is not used.

(Crossover wiring of power supply)

Indoor unit

Pull box

Pull box

Power supply

Power supply

Power supply

Indoor unit

Indoor unit

Breaker

Power supply

9371022642-02_IM.indb   6

9371022642-02_IM.indb   6

2019/10/11   10:00:39

2019/10/11   10:00:39

Summary of Contents for AUXK018GLEH

Page 1: ...CI N UNIT INT RIEURE type cassette UNIDAD INTERIOR Tipo casete Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a cas...

Page 2: ...sult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A r...

Page 3: ...that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such...

Page 4: ...ain piping positions unit mm Drain pipe Connect the attached drain hose 342 293 45 200 140 180 10 80 Gas pipe Liquid pipe Drain pipe Distribution ducts and fresh air inlet positions Distribution duct...

Page 5: ...flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe a...

Page 6: ...age may be blown out If it is impossible to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 10...

Page 7: ...electricity charged in the body may cause malfunction of the PCB Follow the cautions below Establish an earth ground for the indoor and outdoor units and peripheral devices Cut power breaker off Touch...

Page 8: ...en the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Strip 10 mm Ring termina...

Page 9: ...re with solder IMPORTANT Be sure to insulate the connection between the wires Locally purchased Solder and insulate the connected parts Wire kit connector optional parts Wiring arrangement In followin...

Page 10: ...e controller group operates in the same mode When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF No...

Page 11: ...AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigeran...

Page 12: ...ntral remote controller 01 Display only on central remote controller Fan set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stops when the th...

Page 13: ...ed remote control ler error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expan...

Reviews: