AirStage AUXK018GLEH Installation Manual Download Page 3

En-2

2.3.  Accessories

 

WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or other 
prescribed parts. 
The use of non-prescribed parts can cause serious accidents such as the unit to fall, 
water leakage, electric shock, or fire.

The following installation parts are furnished. Use them as required.

Keep the Installation Manual in a safe place and do not discard any other accessories 
until the installation work has been completed.

Name and Shape

Q’ty

Application

Operation manual

1

Installation manual

1

(This book)

Operating Manual 
(CD-ROM)

1

Cable tie (Large)

4

For fixing the connection pipe 
(Large and Small).

Push mount cable tie

1

For transmission and remote 
controller cable binding.

Coupler heat insulation (Small)

1

For indoor side pipe joint 
(Small).

Coupler heat insulation (Large)

1

For indoor side pipe joint 
(Large).

Template (Carton top)

1

For installing indoor unit.

Washer

8

For installing indoor unit.

Insulation

1

For installing drain pipe

Drain hose

1

For installing drain pipe.
VP25 (O.D.32, I.D.25)

Hose band

1

For installing drain hose.

Drain pipe insulation

1

For installing drain pipe.

2.4.  Optional parts

Description

Model

Application

External connect kit

UTY-XWZXZC

For output function.
(Output terminal / CNB01)

UTY-XWZXZB

For control input function.
(Apply voltage terminal / CNA01)

UTY-XWZXZD

For control input function.
(Dry contact terminal / CNA02)

UTY-XWZXZ7

For forced thermostat off function.
(Apply voltage terminal / CNA03)

UTY-XWZXZE

For forced thermostat off function.
(Dry contact terminal / CNA04)

IR receiver kit

UTY-LBHXD

For air conditioner operation.

Human sensor kit

UTY-SHZXC

To prevent waste of electricity, this function 
controls the temperature setting when no 
one is occupying the room.

Wide panel

UTG-AKXA-W

Wide panel hides the gap between the ceil-
ing hole and the Cassette grille.

Description

Model

Application

Panel spacer

UTG-BKXA-W

Installation in a space of 56 mm or greater 
is possible by using panel spacer when the 
height behind the ceiling is low.

Air outlet shutter plate

UTR-YDZK

Install the plate at outlet when carrying out 
3-way direction operation.

Insulation kit for high 
humidity

UTZ-KXRA

Install when the condition under the roof 
is over 80% in humidity and over 30°C in 
temperature.

Fresh air intake kit

UTZ-VXRA

To take fresh air.

Wireless LAN adapter

UTY-TFSXZ*

For wireless LAN control.

External power supply 
unit

UTZ-GXXA

Supply power to the indoor unit PCB when 
the indoor unit is turned off to prevent errors.

3.  INSTALLATION WORK

Correct initial installation location is important because it is difficult to move unit after it is 
installed. 

3.1.  Selecting an installation location

Decide the mounting position together with the customer as follows.

 

WARNING

Select installation locations that can properly support the weight of the indoor. Install the 
units securely so that they do not topple or fall.

 

CAUTION

Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside. 

It will deteriorate metal parts, causing the parts to fail or the unit to leak water.

• Area filled with mineral oil or containing a large amount of splashed oil or steam, such 

as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.

• Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant 
leakage.

• Area that can cause combustible gas to leak, contains suspended carbon fibers or 

flammable dust, or volatile inflammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a fire.

• Area where animals may urinate on the unit or ammonia may be generated.

Do not use the unit for special purposes, such as storing food, raising animals, growing 
plants, or preserving precision devices or art objects. 
It can degrade the quality of the preserved or stored objects.

Do not install where there is the danger of combustible gas leakage.

Do not install the unit near a source of heat, steam, or flammable gas.

Install the unit where drainage does not cause any trouble.

Install the indoor unit, power supply cable, transmission cable, and remote controller 
cable at least 1 m away from a television or radio receivers. The purpose of this is to 
prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under some 
signal conditions.)

If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

Use the “Insulation kit for high humidity” (option), when the condition under the roof 
is over 80% in humidity and over 30°C in temperature. Otherwise, there is a risk of 
condensation on the ceiling.

Decide the mounting position with the customer as follows:

(1)  Install the indoor unit on a place having a sufficient strength so that it withstands 

against the weight of the indoor unit.

(2)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(3)  Leave the space required to service the air conditioner.
(4)  A place from where the air can be distributed evenly throughout the room by the unit.
(5)  Install the unit where connection to the outdoor unit (or RB unit) is easy.
(6)  Install the unit where the connection pipe can be easily installed.
(7)  Install the unit where the drain pipe can be easily installed.
(8)  Install the unit where noise and vibrations are not amplified.
(9)  Take servicing, etc., into consideration and leave the spaces. Also install the unit 

where the filter can be removed.

9371022642-02_IM.indb   2

9371022642-02_IM.indb   2

2019/10/11   10:00:39

2019/10/11   10:00:39

Summary of Contents for AUXK018GLEH

Page 1: ...CI N UNIT INT RIEURE type cassette UNIDAD INTERIOR Tipo casete Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a cas...

Page 2: ...sult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A r...

Page 3: ...that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such...

Page 4: ...ain piping positions unit mm Drain pipe Connect the attached drain hose 342 293 45 200 140 180 10 80 Gas pipe Liquid pipe Drain pipe Distribution ducts and fresh air inlet positions Distribution duct...

Page 5: ...flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe a...

Page 6: ...age may be blown out If it is impossible to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 10...

Page 7: ...electricity charged in the body may cause malfunction of the PCB Follow the cautions below Establish an earth ground for the indoor and outdoor units and peripheral devices Cut power breaker off Touch...

Page 8: ...en the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Strip 10 mm Ring termina...

Page 9: ...re with solder IMPORTANT Be sure to insulate the connection between the wires Locally purchased Solder and insulate the connected parts Wire kit connector optional parts Wiring arrangement In followin...

Page 10: ...e controller group operates in the same mode When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF No...

Page 11: ...AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigeran...

Page 12: ...ntral remote controller 01 Display only on central remote controller Fan set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stops when the th...

Page 13: ...ed remote control ler error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expan...

Reviews: