AirStage AUXK018GLAH Installation Manual Download Page 8

En-7

6.2.  Wiring method

*2

*2

*2

*3

*3

*3

Outdoor unit or RB unit *1

Transmission

Transmission

Indoor unit

Remote controller 

(Master)

Power supply

Indoor unit

Indoor unit

Power supply

Remote 

 control

Breaker

Breaker

Breaker

Remote controller 

(Slave)

Remote controller

*1:  When connecting to the Heat Recovery System, refer to the installation manual of the 

RB unit.

*2:  Earth (Ground) the remote controller if it has an earth (ground) cable.

*3:  The 3-wire type remote controller is not used.

(Crossover wiring of power supply)

Indoor unit

Pull box

Pull box

Power supply

Power supply

Power supply

Indoor unit

Indoor unit

Breaker

Power supply

6.3.  Unit wiring

• Before attaching the cable to terminal block.

6.3.1  Power supply cable

Earth (Ground) 

cable

20 mm

30 mm

A.  For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable. 

(2)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws.  

Do not use a screwdriver that is too small, otherwise, the screw heads may be dam-

aged and prevent the screws from being properly tightened.

(4) 

Do not tighten the terminal screws too much, otherwise, the screws may break.

(5)  See the table for the terminal screw tightening torques.

(6)  Please do not fix 2 power supply cables with 1 screw.

Strip 25 mm

Screw with  

special washer

Screw with  

special washer

Cable end (Loop)

Loop

Terminal block

Cable end (Loop)

Cable

Cable

Do not apply branch wiring. It may result

 electric shock or f

ire.

 

WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 

cables with the ring terminal, the ring terminal's pressure bonding may malfunction and 

cause the cables to abnormally heat up.

B.  For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the figure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-

driver that is too small, otherwise, the screw heads may be damaged and prevent the 

screws from being properly tightened.

(5) 

Do not tighten the terminal screws too much, otherwise, the screws may break.

(6)  See the table for the terminal screw tightening torques.

(7)  Please do not fix 2 power supply cables with 1 screw.

Strip 10 mm

Ring terminal

Sleeve

Screw with  

special washer

Screw with  

special washer

Ring terminal

Terminal block

Ring terminal

Cable

Cable

 

WARNING

Use ring terminals and tighten the terminal screws to the specified torques, otherwise, 

abnormal overheating may be produced and possibly cause heavy damage inside the 

unit.

Terminal number

Tightening torque

M3.5 screw (Power supply/L, N, GND)

1.2 to 1.8 N·m (12 to 18 kgf·cm)

6.3.2  Transmission and Remote controller cable

Transmission cable

Remote controller cable

Shield 

cable 

(no film)

30 mm

45 mm

30 mm

• 

Connect remote controller and transmission cables as shown in Fig. C.

Fig. C

GOOD

Different diameter

Connect to 1 side

PROHIBITED

 

WARNING

Tighten the terminal screws to the specified torques, otherwise, abnormal overheating 

may be produced and possibly cause heavy damage inside the unit.

Tightening torque

M3 screw (Transmission / X1, X2)

(Remote controller / Y1, Y2, Y3)

0.5 to 0.6 N·m

(5 to 6 kgf·cm)

 

CAUTION

To peel the film from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening the 

screw. On the other hand, an undertightened screw can cause faulty contact, which will 

lead to a communication failure.

9371022475_IM.indb   7

2/2/2017   14:58:08

Summary of Contents for AUXK018GLAH

Page 1: ...NUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type cassette UNIDAD INTERIOR Tipo casete Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI...

Page 2: ...ontains no user serviceable parts Always consult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS P...

Page 3: ...that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or t...

Page 4: ...or unit 200 130 50 A B 50 to 100 10 40 140 to 145 Type Dimension mm A B AUXM 246 256 AUXK 288 298 Refrigerant piping and drain piping positions unit mm Drain pipe Connect the attached drain hose 342 2...

Page 5: ...ation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 15 mm or...

Page 6: ...PIPES WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat ex change erosion may occur Insulate the parts properly so that water will not drip from the connection par...

Page 7: ...ce agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth groun...

Page 8: ...1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cable...

Page 9: ...cy stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Force...

Page 10: ...as priority The indoor units within the same remote controller group operates in the same mode When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command Ch1...

Page 11: ...nit address Rotary switch IU AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 When connecting multiple indoor units to 1 refrigerant system set the address at IU AD SW as shown in the T...

Page 12: ...d stop Error report target 47 00 All Change the target for reporting errors Errors can either be re ported in all locations or only on the central remote controller 01 Display only on central remote c...

Page 13: ...mmunica tion circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2...

Reviews: