background image

En-10

Operation behavior

Connector

Output voltage

Status

CNB01

External output 1 

Pins 1-2

0V

Stop

DC 12 V

Operation

External output 2 

Pins 1-3

0V

Normal

DC 12 V

Error

External output 3  

Pins 1-4

0V

Indoor unit fan stop

DC 12 V

Indoor unit fan operation

6.5.3  Connection methods

Wire modification

(1) 

Remove insulation from wire attached to wire kit connector.

(2)  Remove insulation from field supplied cable. Use crimp type insulated butt connector 

to join field cable and wire kit wire.

(3)  Connect the wire with connecting wire with solder.

IMPORTANT:

Be sure to insulate the connection between the wires.

Locally purchased

Solder and insulate the connected parts.

Option parts: 

External input /output wire

Connection terminals and wiring arrangement

In following figure, all the possible connectors are connected for description.

In actual installation, you cannot connect all the connectors at once.

1

2

3

CNB01

CNA01

CNA02

CNA03

CNA04

Cable hooks

Cable clamp

7.  FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.

Please set by either of the methods.

Each setting method is described in below (1) to (3).
(1) IU AD, REF AD SW settings: This section (7.1. Setting the address)
(2) Remote controller settings:

Refer to the wired or wireless remote controller manual 

for detailed setting information. (Set IU AD, REF AD 

SW to 0)

(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting 

information. (Set IU AD, REF AD SW to 0)

7.1.  Setting the address

 

CAUTION

Use an insulated screwdriver to set the dip switches.

• 

Open the cover referring to the figure below. Close and fix the cover after addressing 

setting.

(1) Loosen the screw.

(2) Slide the cover and open it.

IU  AD

REF AD

RC AD

×10              ×1

×10             ×1

SET3

SET4

For refrigerant 

circuit address

For indoor 

unit address

7.1.1  Indoor unit address

• Rotary switch (IU AD × 1)...Factory setting “0”

• Rotary switch (IU AD × 10)...Factory setting “0”

When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD 

SW as shown in the Table A.

7.1.2  Refrigerant circuit address

• Rotary switch (IU AD × 1)...Factory setting “0”

• Rotary switch (IU AD × 10)...Factory setting “0”

In the case of  multiple refrigerant systems, set REF AD SW as shown in the Table A for 

each refrigerant system.

Set to the same refrigerant circuit address as the outdoor unit.

Setting

Setting range

Type of switch

Indoor unit address

0 to 63

Setting 

example 2

IU AD × 10

IU AD × 1

Refrigerant circuit 

address

0 to 99

Setting ex-

ample 63

REF AD × 10

REF AD × 1

• If working in an environment where the wireless remote controller can be used, the ad

-

dresses can also be set using the remote controller.

• 

If setting the addresses using the wireless remote controller, set the indoor unit address 

and refrigerant circuit address to “00”. 

 

(For information on setting using the wireless remote controller.)

Table A

Address

Rotary switch setting

Address

Rotary switch setting

Refrigerant 

circuit

REF AD SW

Indoor unit

IU AD SW

× 10

× 1

× 10

× 1

0

0

0

0

0

0

1

0

1

1

0

1

2

0

2

2

0

2

3

0

3

3

0

3

4

0

4

4

0

4

5

0

5

5

0

5

6

0

6

6

0

6

7

0

7

7

0

7

8

0

8

8

0

8

9

0

9

9

0

9

10

1

0

10

1

0

11

1

1

11

1

1

12

1

2

12

1

2

. . 

.

. . 

.

. . 

.

. . 

.

. . 

.

. . 

.

99

9

9

63

6

3

Do not set the indoor unit address (IU AD SW) at 64 to 99. 

It may result in failure.

7.2.  Custom code setting

• 

Selecting the custom code prevents the indoor unit mix-up. (figure below) 

(Up to 4 codes can be set.)

• 

Perform the setting for both the indoor unit and the remote controller.

Code change

Indoor unit

Remote 

controller

Confusion

A            B              C           D

A           B            C             D

• Custom code setting for indoor unit

Set the DIP switch SET3 SW1, 2, referring to the 

figure and table below.

IU  AD

REF AD

RC AD

×10              ×1

×10             ×1

SET3

SET4

DIP switch “SET3”

SW

1

SW

2

SW

3

SW

4

ON 

OFF

DIP switch “SET3”

DIP switch 

SET3

Custom code

A (Factory 

setting)

B

C

D

SW1

OFF

ON

OFF

ON

SW2

OFF

OFF

ON

ON

9371022475_IM.indb   10

2/2/2017   14:58:13

Summary of Contents for AUXK018GLAH

Page 1: ...NUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type cassette UNIDAD INTERIOR Tipo casete Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI...

Page 2: ...ontains no user serviceable parts Always consult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS P...

Page 3: ...that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or t...

Page 4: ...or unit 200 130 50 A B 50 to 100 10 40 140 to 145 Type Dimension mm A B AUXM 246 256 AUXK 288 298 Refrigerant piping and drain piping positions unit mm Drain pipe Connect the attached drain hose 342 2...

Page 5: ...ation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 15 mm or...

Page 6: ...PIPES WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat ex change erosion may occur Insulate the parts properly so that water will not drip from the connection par...

Page 7: ...ce agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth groun...

Page 8: ...1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cable...

Page 9: ...cy stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Force...

Page 10: ...as priority The indoor units within the same remote controller group operates in the same mode When function setting is Emergency stop mode In the case of Edge input Connector Input signal Command Ch1...

Page 11: ...nit address Rotary switch IU AD 1 Factory setting 0 Rotary switch IU AD 10 Factory setting 0 When connecting multiple indoor units to 1 refrigerant system set the address at IU AD SW as shown in the T...

Page 12: ...d stop Error report target 47 00 All Change the target for reporting errors Errors can either be re ported in all locations or only on the central remote controller 01 Display only on central remote c...

Page 13: ...mmunica tion circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2...

Reviews: