6.1. Electrical requirement

Voltage rating

208/230 V

Operating range

187 to 253 V

• Select the power cable type and size in accordance with relevant local and national 

regulations.

• Speci

fi

 cations for local wiring power cord and branch wiring are in compliance with local 

code.

• Select the correct cable type and size according to the country or region’s regulations.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Refer to the table for the breaker speci

fi

 cations of each installation condition. Perform 

the power crossover wiring within the range of the same refrigerant system. When the 
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 
below.

A. Current breaker requirements

Model

MCA

MAX. CKT. BKR (Fuse capacity)

AUUB18TLAV

0.43 A

15 A

AUUB24TLAV

0.43 A

AUUB30TLAV

0.68 A

AUUB36TLAV

0.68 A

MCA: Minimum Circuit Ampacity
MAX. CKT. BKR : Maximum Circuit Breaker

When the power crossover wiring is done, make it so that the total of the MCA of the 
connected RB units and indoor units does not exceed the 11 A. For RB unit  MCA, refer to 
the RB unit  installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add 
breakers or use a breaker with a greater capacity.

B. Ground Fault Equipment Breaker requirements

Breaker capacity

* Maximum connectable  “indoor units” 

or “indoor units + RB units”

30 mA, 0.1 sec or less

36 or less **

100 mA, 0.1 sec or less

37 to 90

* Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
**  If the total number of units connected to the breaker exceeds 36, either add a 30mA 

breaker, or use breakers with a greater capacity.

6.1.1. Cable speci

fi

 cations

Recommended 

cable size

Cable type

Remark

Transmission cable

22 AWG

(0.33 mm²)

LONWORKS 
compatible cable

22 AWG LEVEL 4 
(NEMA) 
non-polar 2 core, 
twisted pair solid core 
diameter 0.026 in. 
(0.65 mm)

Remote controller 
cable (2-wire type)

22 AWG to 16 AWG

(0.33 mm² to 1.25 mm²)

Sheathed PVC 
cable

Non polar 2 core

Remote controller 
cable (3-wire type)

22 AWG

(0.33 mm²)

Sheathed PVC 
cable

Polar 3 core

6.2. Wiring method

EXAMPLE

Outdoor unit or RB unit *1

Transmission

Transmission

Power supply

Breaker2

Breaker2

Breaker2

Breaker1

Breaker1

Breaker1

Power supply

Remote controller

(Master)

Remote controller

(Slave)

Remote controller

Indoor unit

Remote 

control

*2

*2

*2

Indoor unit

Indoor unit

Breaker 1:  Ground Fault Equipment

Breaker (GFEB)

Breaker 2:  Maximum Circuit Breaker

(MAX. CKT. BKR)

Breaker shall be located in sight from and readily accessible from all indoor units.
*1: When connecting to the Heat Recovery System, refer to the installation manual of the 

RB unit. 

*2: When connecting the 2-wire type remote controller, Y3 is not used.

Indoor unit

Power supply

Pull box

Pull box

Breaker2

Breaker1

Power supply

Power supply

Power supply

: Disconnect switch

Indoor unit

Indoor unit

(Crossover wiring of power supply)

Disconnect switch shall be installed between indoor unit and pull box.

6.3. Unit wiring

• Before attaching the cable to terminal block.

6.3.1.

 

Power supply cable

Conduit connector

Earth (ground) 
wire

7-1/16 in. (180 mm)

7-1/16 in. (180 mm)

A.  For solid core wiring

(1) To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable. 

(2) Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3) Use an appropriate screwdriver to tighten the terminal screws. 
  Do not use a screwdriver that is too small, otherwise, the screw heads may be 

damaged and prevent the screws from being properly tightened.

(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not 

fi

 x 2 power supply cables with 1 screw.

9371022314-03_IM.indb   Sec1:8

9371022314-03_IM.indb   Sec1:8

10/23/2013   2:59:36 PM

10/23/2013   2:59:36 PM

Summary of Contents for AUUB18TLAV

Page 1: ...authorized service personnel only Français MANUEL D INSTALLATION APPAREIL INTÉRIEUR type cassette Pour le personnel agréé uniquement AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV Español MANUAL DE INSTALACIÓN UNIDAD INTERIOR Tipo casete Únicamente para personal de servicio autorizado ...

Page 2: ... valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the cu...

Page 3: ...llation Manual in a safe place and do not discard any other accessories until the installation work has been completed Name and Shape Q ty Application Operation Manual 1 Installation Manual 1 This book Cable tie Large 4 For fixing the connection pipe Large and Small Cable tie Medium 2 For transmission and remote controller cable binding Coupler heat insulation Small 1 For indoor side pipe joint Sm...

Page 4: ...iling Function setting H in mm AUUB18 AUUB24 AUUB30 AUUB36 Standard mode 118 3 000 118 3 000 125 3 200 125 3 200 High Ceiling mode 137 3 500 137 3 500 141 3 600 165 4 200 Be sure to make the function settings with the remote controller according to the installed ceiling height Discharge Direction Setting The discharge direction can be selected as shown below 4 DIRECTION 3 DIRECTION 4 in 100 mm or ...

Page 5: ...o M10 3 3 2 Hanging preparations Firmly fasten the hanging bolts as shown in the figure or by another method Install the hanging bolts at a place where they would be capable of holding a weight of at least 110 lbf 490 N per bolt Hole in anchor Hole in plug Concrete Insert Hanging bolt M10 Field supply 3 3 3 Body installation 1 Install the attached washer and nut prepared on site onto the hanging b...

Page 6: ...ed humidity exceeds 80 use heat insulation that is 13 16 in 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 68 F 20 C 4 3 Flare connection pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tighten...

Page 7: ...ulation After installing the Coupler heat insulation wrap both ends with vinyl tape so that there is no gap Cable tie Large Accessories Body Be sure to overlap the insulation Coupler heat insulation Coupler heat insulation Accessories No gap CAUTION Must fit tightly against body without any gap 5 INSTALLING DRAIN PIPES WARNING Do not insert the drain piping into the sewer where sulfurous gas occur...

Page 8: ...es or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection...

Page 9: ...22 AWG 0 33 mm LONWORKS compatible cable 22 AWG LEVEL 4 NEMA non polar 2 core twisted pair solid core diameter 0 026 in 0 65 mm Remote controller cable 2 wire type 22 AWG to 16 AWG 0 33 mm to 1 25 mm Sheathed PVC cable Non polar 2 core Remote controller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method EXAMPLE Outdoor unit or RB unit 1 Transmission Transmission Pow...

Page 10: ...rew Power supply L1 L2 N GND 11 to 16 lbf in 1 2 to 1 8 N m 6 3 2 Transmission and Remote controller cable Shielded wire no film 1 9 16 in 40 mm 1 3 16 in 30 mm Transmission cable Remote controller cable For 3 wire type For 2 wire type 1 3 16 in 30 mm 1 3 16 in 30 mm When the 2 cables are attached GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the speci...

Page 11: ...using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 492 ft 150 m Use an external input and output cable with appropriate external dimension depending o...

Page 12: ...ut signal Command Ch1 of CNA01 or CNA02 OFF ON Emergency stop ON OFF Normal In the case of Pulse input Connector Input signal Command CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal All indoor units of same refrigerant system stops when Emergency stop operates When function setting is Forced stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON ...

Page 13: ...ibed 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing...

Page 14: ...emote controller The remote controller is optional equipment Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 Refer to 7 1 Setting the address for indoor unit address and refrigerant circuit ad dress settings Turn the power of the indoor unit ON before starting the setting Turning on the power to the indoor units initializes EEV so m...

Page 15: ...a ture 2 Operating temperature switching of external heaters 62 00 Setting 0 Sets the temperature conditions when the external heater is ON For the temperature conditions see Temperature conditions when the external heater is ON For a more detailed explanation see the Design Technical Manual 01 Setting 1 02 Setting 2 03 Setting 3 04 Setting 4 05 Setting 5 Temperature conditions when the external h...

Page 16: ... Does water drain easily from the indoor units Water leakage Is the voltage of the power source the same as that indicated on the label on the indoor unit No operation heat or burn damage Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage...

Page 17: ...e Error icon Touch the Status Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller Touch the Next Page or previous page to switch to other indoor unit information ...

Reviews: