AirStage ASHA18GACH Installation Manual Download Page 5

En-4

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [mm (in.)]

Thickness [mm]

6.35 (1/4)

0.80

9.52 (3/8)

0.80

12.70 (1/2)

0.80

15.88 (5/8)

1.00

19.05 (3/4)

1.20

1

4.2. Pipe requirement

 

CAUTION

Refer to the installation manual for the outdoor unit for description of allowable pipe 
length and height difference.

Use pipe with water-resistant heat insulation.

 

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may 
cause water leaks. 
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only) 
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70 %, install heat insulation around the refrigerant piping. 
If the expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or 
thicker and if the expected humidity exceeds 80 %, use heat insulation that is 20 mm 
or thicker. If heat insulation is used that is not as thick as speci

fi

 ed, condensation may 

form on the surface of the insulation. 
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less 
(at 20 °C).

1

4.3. Flare connection (pipe connection)

 

WARNING

Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

4.3.1. Flaring

Use special 

fl

 are tool exclusive for R410A.

(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3)  Insert the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor and outdoor units (or 

RB unit) respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. 

Use the special R410A 

fl

 are tool. Leakage of refrigerant may result if other 

fl

 are nuts 

are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Check if [L] is 

fl

 ared uniformly and 

is not cracked or scratched.

Die

Pipe

A

B

L

Pipe outside 

diameter [mm (in.)]

Dimension A [mm]

Dimension B

-

0

0.4 

[mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional (R22) 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should 

be approximately 0.5 mm more than indicated in the table (for 

fl

 aring with R410A 

fl

 are 

tools) to achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimension A. 

It is recommended that a R410A 

fl

 aring tool is used.

[For 

1

 Rear piping, 

2

 Right piping and 

3

 Bottom piping]

•  The drain hose and drain cap are used as they are.

[For 

4

 Left bottom piping, 

5

 Left piping and 

6

 Center piping, 

7

 Left 

rear piping]

•  Remove the drain cap and drain hose. Mount the drain cap and drain hose to the drain 

port on its opposite side. 

Left side

Right side

Drain cap

Drain hose

Drain cap

Drain hose

Insert the drain hose until it butts 
against the drain port.

Insert the drain cap until it butts 
against the drain port.

3.3.4. Cut-out for piping on front cover

[For 

2

 Right piping, 

3

 Bottom piping, 

4

 Left bottom piping and 

5

 

Left piping]

•  Use a metal shears or other cutting tool to cut along the groove in the plastic for the 

piping that will coming out of the front cover.

For 

2

 Right piping

For 

5

 Left piping

For 

4

 Left bottom piping

For 

3

 Bottom piping

4. PIPE INSTALLATION

]

 

CAUTION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant R410A models. Also, when storing the piping, securely seal the openings 
by pinching, taping, etc.

While welding the pipes, be sure to blow dry nitrogen gas through them.

]1

4.1. Selecting the pipe material

 

CAUTION

Do not use existing pipes from another refrigeration system or refrigerant.

Use pipes that have clean external and internal sides without any contamination which 
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.

It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.

Do not use copper pipes that have a collapsed, deformed, or discolored portion 
(especially on the interior surface). Otherwise, the expansion valve or capillary tube 
may become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary 
to choose adequate materials.

•  Thicknesses of copper pipes used with R410A are as shown in the table.
•  Never use copper pipes thinner than those indicated in the table even if they are 

available on the market.

9373370147-02_IM.indb   4

9373370147-02_IM.indb   4

1/21/2013   4:10:12 PM

1/21/2013   4:10:12 PM

Summary of Contents for ASHA18GACH

Page 1: ...APPAREIL INT RIEUR Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTE...

Page 2: ...rvice person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 1 2 1 Precautions for using R410A refrigerant WARNING Do no...

Page 3: ...ates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Are...

Page 4: ...y strong so that the wall can support the weight Fig A UNIT mm UNIT centre UNIT size UNIT size hole hole hole for tapping screw 80 hole 80 hole Piping inlet Piping inlet hole hole hole hole hole hole...

Page 5: ...flare R410A pipes the dimension A should be approximately 0 5 mm more than indicated in the table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure...

Page 6: ...breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break For 1 Rear piping 2 Right piping and 3 Bottom piping Install the indoor unit piping in the direct...

Page 7: ...ly making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as overheating the terminals...

Page 8: ...1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cabl...

Page 9: ...ld be separate from the power cable line 6 3 3 Remote controller cable Remote controller cable modification 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remo...

Page 10: ...d at the input device you want to connect use the Apply voltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 t...

Page 11: ...operation 3 Connection methods Wire modification Remove insulation from wire attached to wire kit connector Remove insulation from field supplied cable Use crimp type insulated butt connector to join...

Page 12: ...frigerant system set the address at IU AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD 1 Factory setting 0 Rotary switch REF AD 10 Factory setting 0 In the case of mul...

Page 13: ...oling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18 to 32 C NOTE Please do not make a standard setup and an extension setup intermingled in remote controller group...

Page 14: ...lamp Green FILTER indicator lamp Red TIMER indicator lamp Orange 7 4 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function sett...

Page 15: ...6 Center piping and 7 Left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with vinyl tape so that there is no gap 1 Rear 2 Right and...

Page 16: ...ge Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat...

Page 17: ...n manual of the remote controller 2 digit numbers are corresponding to the error code in the preceding table Touch the Next Page or previous page to switch to other indoor unit information UTY RNKY UT...

Reviews: